FIGURE 6-16 - Flue Terminal Location
All vent pipe and combustion air pipe and fittings shall comply with the following:
Materials used in the U.S. must comply with the following standards:
ANSI/ASTM D1785, ANSI/ASTMD2661, ANSI/ ASTM F441.
INSIDE
CORNER
DETAIL
G
V
H
D
A
E
B
L
C
B
V
B
Fixed
Closed
V
I
V
F
V
Fixed
Closed
Operable
Operable
M
V
B
V
K
J
B
V
VENT
TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS
NOT
PERMITTED
Vent Termination Minimum Clearances
US Installations
Canadian Installations
A
Clearance above grade, veranda, porch, deck, or balcony
12" (305mm)
12" (305mm)
B
Clearance to window or door that may be opened
12" (305mm)
3 ft. (0.9m)
C
Clearance to permanently closed window
*12" (305mm)
*12" (305mm)
D
Vertical Clearance to ventilated soffit located above the terminal within a
horizontal distance of 2 feet (610 mm) from the center line of the terminal
18" (457mm)
18" (457mm)
E
Clearance to unventilated soffit
18" (457mm)
18" (457mm)
F
Clearance to outside corner
9" (229mm)
9" (229mm)
G
Clearance to inside corner
36" (456mm)
36" (456mm)
H
Clearance to each side of center line extended above meter/ regulator
assembly
3 ft. (0.9m) within a height of 15 ft.
(4.5m) above the meter/ regulator
assembly
3 ft. (0.9m)
I
Clearance to service regulator vent outlet
3 ft. (0.9m)
3 ft. (0.9m)
J
Clearance to non-mechanical air supply inlet to building or the combustion
air inlet to
any other appliance
12" (305mm)
3 ft. (0.9m)
K
Clearance to mechanical air supply inlet
*3 ft. (0.9m)
6 ft. (1.8m)
L
Clearance above paved sidewalk or paved driveway located on public
property
*7 ft. (2.1m)
7 ft. (2.1m) †
M
Clearance under veranda, porch, deck or balcony
*12" (305mm) ‡
12" (305mm)‡
† A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
*For clearances not specified in ANSI Z223.1/NFPA 54 or
CSA B149.1, clearance will be in accordance with local
installation codes and the requirements of the gas supplier
and these installation instructions.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a
minimum of one side beneath the floor.
Note:
Local Codes or Regulations may require different clearances. Flue terminal must be exposed to external air and position must
allow the free passage of air across it at all times. In certain weather conditions the terminal may emit a plume of steam. Avoid
positioning terminal where this may cause a nuisance.
6 - COMBUSTION AIR AND VENT PIPING
Summary of Contents for DCB-125
Page 2: ...DCC 205 ...
Page 4: ...DCB 165 ...
Page 65: ...61 APPENDIX A WIRING DIAGRAMS A 1 MODELS 125 Heat Only 240011947 REV B 03 31 2018 ...
Page 66: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240011947 REV B 03 31 2018 ...
Page 67: ...63 APPENDIX A WIRING DIAGRAMS A 3 MODELS 150 Combi 240011947 REV B 03 31 2018 ...
Page 68: ...64 APPENDIX A WIRING DIAGRAMS A 4 MODELS 205 Combi 240011947 REV B 03 31 2018 ...
Page 69: ...65 NOTES 240011947 REV B 03 31 2018 ...
Page 70: ...66 NOTES 240011947 REV B 03 31 2018 ...
Page 81: ...9 125 WITH ZONE CIRCULATOR PUMPS 125 with Zone Circulator Pumps PN 240011430 REV G 03 31 18 ...
Page 84: ...12 125 WITH ZONE VALVES PIPING DIAGRAM 125 with Zone Valves PN 240011430 REV G 03 31 18 ...
Page 90: ...18 165 with Zone Valves 165 WITH ZONE VALVES PIPING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 94: ...22 150 205 WITH ZONE PUMPS WIRING DIAGRAM 150 205 With Zone Pumps PN 240011430 REV G 03 31 18 ...
Page 102: ...30 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 103: ...31 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 104: ...32 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 105: ...33 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 110: ...38 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV G 03 31 18 ...
Page 111: ...39 NOTES PN 240011430 REV G 03 31 18 ...
Page 112: ......
Page 115: ......
Page 116: ......