58
13.1 Error Messages And Resetting The Boiler
Error Description
Operation
09
Gas valve connection fault
Check cable PCB/gas valve and gas valve plug
10
Outdoor sensor fault
Check sensor and cable
15
Gas valve command fault
Verify all cables. Replace PCB.
Call authorized SERVICE center
20
Central Heating NTC sensor fault
Check sensor and cable
28
Flue NTC heat exchanger sensor fault
Check sensor and cable
40
Return NTC sensor fault
Check sensor and cable
50
Domestic Hot Water NTC sensor fault
Check sensor and cable
53
Obstruction in flue pipe, Recirculation, Out of
Calibration, Poor gas quality
Check for obstruction in flue pipe. Check for recirculation,
recalibrate, check gas quality
55
PCB not programmed
Call authorized SERVICE center
83-84-85
86-87
Communication problem between boiler board and
control unit
Probable short circuit on wiring.
Check cable between control unit and boiler
109
Pre-circulation alarm (temporary fault)
Check correct circulation of water and pump. Check supply
and return wiring is correct.
110
Safety thermostat tripped due to over temperature
(pump probably blocked or air in heating circuit)
Check safety thermostat and cable; check correct circulation
of water and pump
118
Hydraulic pressure too low.
Refill heating system by opening cold water tap
117
Hydraulic pressure too high.
Relieve pressure via relief valve or drain. Ensure water feed
is operating correctly.
125
No circulation of water
(control performed via temperature sensor).
Check correct circulation of water and pump.
Check correct connection of NTC sensor on pipe
128
Loss of flame
Check sensing electrode and cable, flue recirculation,
electrical continuity between burner and ground.
Enable automatic calibration.
Call authorized SERVICE center.
130
NTC flue sensor tripped due to over temperature
Check thermostat, correct circulation of water and pump.
Check status of primary exchanger.
131
Thermo fuse tripped due to over temperature or
wire harness disconnected from thermo fuse, off
the board, or wire harness may be cut.
Check thermo fuse, correct circulation of water and
pump. Check status of primary exchanger. Replace
heat exchanger. Call authorized SERVICE center.
Verify wire harness installation and continuity.
133
Ignition failure
Check correct operation of condensate trap.
Check sensing electrode, spark electrode and cable.
Check flue recirculation, electrical continuity between
burner and ground. Enable automatic calibration function.
Call authorized SERVICE center
134
Gas supply valve blocked
Check gas pressure, sensing electrode, spark
electrode and cable, replace PCB if it necessary.
Call authorized SERVICE center
135
Internal error
Verify all cables. Replace PCB.
Call authorized SERVICE center
160
Fan fault
Check fan and cable
162/317
Incorrect power supply frequency.
Incorrect power supply frequency.
169
Flue pressure switch (contact open)
Check pressure switch and cable.
Check obstruction on flue pipe
164/384
Fault flame (parasitic flame).
Check correct operation of T. gas valve.
165/385
Input voltage too low.
Check power supply
To RESET boiler press
button for at least 2 seconds.
For other error codes not described in table please contact
manufacturer at 1(800) 325-5479.
13 - TROUBLE SHOOTING
240011947 REV B, [03/31/2018]
Summary of Contents for DCB-125
Page 2: ...DCC 205 ...
Page 4: ...DCB 165 ...
Page 65: ...61 APPENDIX A WIRING DIAGRAMS A 1 MODELS 125 Heat Only 240011947 REV B 03 31 2018 ...
Page 66: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240011947 REV B 03 31 2018 ...
Page 67: ...63 APPENDIX A WIRING DIAGRAMS A 3 MODELS 150 Combi 240011947 REV B 03 31 2018 ...
Page 68: ...64 APPENDIX A WIRING DIAGRAMS A 4 MODELS 205 Combi 240011947 REV B 03 31 2018 ...
Page 69: ...65 NOTES 240011947 REV B 03 31 2018 ...
Page 70: ...66 NOTES 240011947 REV B 03 31 2018 ...
Page 81: ...9 125 WITH ZONE CIRCULATOR PUMPS 125 with Zone Circulator Pumps PN 240011430 REV G 03 31 18 ...
Page 84: ...12 125 WITH ZONE VALVES PIPING DIAGRAM 125 with Zone Valves PN 240011430 REV G 03 31 18 ...
Page 90: ...18 165 with Zone Valves 165 WITH ZONE VALVES PIPING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 94: ...22 150 205 WITH ZONE PUMPS WIRING DIAGRAM 150 205 With Zone Pumps PN 240011430 REV G 03 31 18 ...
Page 102: ...30 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 103: ...31 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 104: ...32 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 105: ...33 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Page 110: ...38 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV G 03 31 18 ...
Page 111: ...39 NOTES PN 240011430 REV G 03 31 18 ...
Page 112: ......
Page 115: ......
Page 116: ......