Duomo gas proving systems

-

Duomo gas detection

-

Duomo carbon dioxide sensors

-

Duomo ventilation interlocks

-

Are available direct or from all major stockists

BX116 operation

Maintenance procedure

This detector must be function checked as described above using calibrated test gas every 6 months. To arrange for a
Duomo engineer to conduct this work or to arrange a service contract please call 01905 797989.

Before powering up the BX116 once again check that all electrical connections are correct.

1. Apply 230V supply to the Ph and N terminals. Ensure that the correct fuse is used in the supply. (3 or 5A max.)

2. All of the lights on the fascia will light up in turn. This will take approximately 20 seconds. This checks the function of

all the L.E.D.'s.

3. The ON L.E.D. will remain flashing for about 90 seconds. This is the sensor warm-up period. The gas detector will not

provide gas detection during this period. When the ON light becomes constant the detector is in operation.

4. By pushing and maintaining pressure on the manual TEST button a function test can be performed for all pre-alarm

relays and main alarm relay, together with L.E.D.'s and audible alarm.

The sequence will be:

a) The 8% L.E.L. / 120

ppm

and Pre-Alarm 1 L.E.D. will be actuated. The Pre-Alarm 1 relay will be changed over.

b) The 20% L.E.L. / 300

ppm

and Main Alarm L.E.D. will be actuated. The Main Alarm relay will be changed over. The

relevant Alarm L.E.D.'s will light to show which zones are in alarm.

By releasing the the manual TEST button the lights will go out and the audible alarm will cease. If a latched alarm
function on the main relay is configured this will remain on until the RESET button is pressed.

5. In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas. The maximum

concentrations are;

- 40% L.E.L. for methane in air
- 350

ppm

for carbon monoxide

- 0.85% (MOL) for propane

Any higher than this can reduce sensor life. NOTE: NEVER TEST USING NEAT GAS. THIS WILL POISON THE SENSOR.

6. To simulate a sensor fault situation disconnect the sensor plug. The detector will go into a FAULT alarm and the sensor

fault relay will be actuated. This will close the contacts between terminals 4 and 5 and open the contacts between
terminals 10 and 12 (Main Alarm relay). When the plug is reconnected the detector can be reset.

Summary of Contents for BX116

Page 1: ...ly and alarm circuit wiring and the second is for connecting the sensor wiring This reduces the chance of incorrect site wiring The front panel has two banks of eight lights indicating in rotation which probe is currently monitoring and a bright display showing the LEL or PPM gas concentration measured Operation When the remote sensor detects the presence of the target gas a 4 20mA signal is sent ...

Page 2: ...ated 11 Main Alarm Zone 2 20 L E L concentration of gas detected in Zone 2 Main alarm relay actuated 12 LEL L E D This lights when the jumper switch for display data is set to read in lower explosive limit LEL 13 Zone 2 Indication These L E D s represent the Zone 2 sensors and flash when a sensor is connected 14 No of Sensors Switches DIP switches allowing you to select how many sensors can be att...

Page 3: ...ed using this particular board and therefore will not function correctly with any other Important Notes Always check the wiring before powering up the system Do not test this sensor with anything other than Duomo test gas see BX116 Operation section for further information Concentrations above this will damage the sensor and shorten sensor life The installation of this gas detector does not releas...

Page 4: ...play units The BX116 can display the current gas concentration detected in either LEL or ppm This is done by closing one of two jumpers on the PCB on the rear of the door of the unit Closing the upper jumper sets the unit to LEL Closing the lower jumper sets the unit to ppm Disabling or uninstalling sensors The BX116 can accept up to 16 sensors divided into two zones You should deselect the DIP sw...

Page 5: ...be performed for all pre alarm relays and main alarm relay together with L E D s and audible alarm The sequence will be a The 8 L E L 120ppm and Pre Alarm 1 L E D will be actuated The Pre Alarm 1 relay will be changed over b The 20 L E L 300ppm and Main Alarm L E D will be actuated The Main Alarm relay will be changed over The relevant Alarm L E D s will light to show which zones are in alarm By r...

Page 6: ...tion and the main gas valve is not closing There is no supply to the solenoid valve Check that the plug is inserted correctlty Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sens...

Page 7: ...for this product will become void if damage is caused by the installer Technical specification Power Supply 230V AC 50Hz 10 Secondary Battery 12V DC 10 Power Consumption 30W maximum 230V Power Consumption 25W maximum 12V Relay contact range 10A 230V resistive 5A 30V DC resistive 1st pre alarm Can be set from 8 L E L 120ppm to 13 250ppm of LEL Main alarm Fixed at 20 L E L 300ppm Sensor fault Short ...

Reviews: