Troubleshooting

In case of alarm

Extinguish any naked flames.
Do not switch lights or electrical devices on or off.
Open all windows and doors to increase ventilation.
If the 'ALARM' L.E.D. is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause
of the alarm.
If the alarm sound remains constant, and the cause is not evident or possible to eliminate turn off the emergency
isolation valves to the area and contact your gas provider emergency line. They will advice accordingly.

If you are experiencing difficulties, having made the checks listed above call Duomo on 01905 797989 for
technical assistance.

The Problem

The Solution

No lights are illuminated on the fascia of the detector

Check that the electrical supply is reaching the
device and that the plug in terminal rail is pushed
into place.

One or all of the sensor fault lights are illuminated

Sensor fault continues to alarm

The detector is subject to repeated alarms

The detector is in a main alarm condition and the
main gas valve is not closing

There is no supply to the solenoid valve

Check that the plug is inserted correctlty.

Check that the sensor wiring is correctly terminated
at both the sensor and detector. Check that 12V DC
is present at the sensor. The green light on the sensor
should be illuminated. Pressing the TEST button it is
possible to check the efficiency of the device and if
the sensors have been connected correctly.

Check that the connections are correct and that
power is supplied to the valve i.e. the valve is not
stuck in the open position. The function of the alarm
relays both Pre-Alarm and Main Alarm can be
checked by pressing the TEST button on the detector
fascia. Check that the main alarm action is configured
for a latching alarm (Switch 2 on 4th DIP switch).

Check the sensor wiring. If the red Overload LED is lit
a short circuit or overload has occurred on the sensor
or the connecting cable.

Ensure that there is not an occassional gas leak. This
may be due to a valve or joint which leaks under
pressure.

The Main Alarm relay is a volt-free contact, therefore
you must connect the live supply to the common of
the main alarm relay contacts terminal 10. A supply
wil then come from terminal 12 to the solenoid valve.

Sensor is connected, but no L.E.D. is lit on the front
fascia

Check that the DIP switch is set to the ON position

Summary of Contents for BX116

Page 1: ...ly and alarm circuit wiring and the second is for connecting the sensor wiring This reduces the chance of incorrect site wiring The front panel has two banks of eight lights indicating in rotation which probe is currently monitoring and a bright display showing the LEL or PPM gas concentration measured Operation When the remote sensor detects the presence of the target gas a 4 20mA signal is sent ...

Page 2: ...ated 11 Main Alarm Zone 2 20 L E L concentration of gas detected in Zone 2 Main alarm relay actuated 12 LEL L E D This lights when the jumper switch for display data is set to read in lower explosive limit LEL 13 Zone 2 Indication These L E D s represent the Zone 2 sensors and flash when a sensor is connected 14 No of Sensors Switches DIP switches allowing you to select how many sensors can be att...

Page 3: ...ed using this particular board and therefore will not function correctly with any other Important Notes Always check the wiring before powering up the system Do not test this sensor with anything other than Duomo test gas see BX116 Operation section for further information Concentrations above this will damage the sensor and shorten sensor life The installation of this gas detector does not releas...

Page 4: ...play units The BX116 can display the current gas concentration detected in either LEL or ppm This is done by closing one of two jumpers on the PCB on the rear of the door of the unit Closing the upper jumper sets the unit to LEL Closing the lower jumper sets the unit to ppm Disabling or uninstalling sensors The BX116 can accept up to 16 sensors divided into two zones You should deselect the DIP sw...

Page 5: ...be performed for all pre alarm relays and main alarm relay together with L E D s and audible alarm The sequence will be a The 8 L E L 120ppm and Pre Alarm 1 L E D will be actuated The Pre Alarm 1 relay will be changed over b The 20 L E L 300ppm and Main Alarm L E D will be actuated The Main Alarm relay will be changed over The relevant Alarm L E D s will light to show which zones are in alarm By r...

Page 6: ...tion and the main gas valve is not closing There is no supply to the solenoid valve Check that the plug is inserted correctlty Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sens...

Page 7: ...for this product will become void if damage is caused by the installer Technical specification Power Supply 230V AC 50Hz 10 Secondary Battery 12V DC 10 Power Consumption 30W maximum 230V Power Consumption 25W maximum 12V Relay contact range 10A 230V resistive 5A 30V DC resistive 1st pre alarm Can be set from 8 L E L 120ppm to 13 250ppm of LEL Main alarm Fixed at 20 L E L 300ppm Sensor fault Short ...