Exercises for each function
-
ZERO TRIM
- Executing the menu to put ZERO+SPAN button.
- Moving to the sub directory to put Span button when 1 TRIM message appear.
- Executing Zero Trim Function to put the Span button when 11 Z-TRIM message appear.
- If “SAVE” is displayed, push SPAN Button to save set-up value.
-
Zero Adjustment : To change the PV value as 14
- Executing the menu to put ZERO+SPAN button.
- Moving to the sub directory to put Span button when 1 TRIM message appear.
- Moving to next menu to put Zero button when 11 Z-TRIM message appear.
- Executing Zero Adjustment function to put Span button when 12 Z-ADJ message appear.
- LCD displays
‘
0.0
’
and the highest input DIGIT flickers.
- If the flickering DIGIT is not tens place, push ZERO+SPAN button until tens place flickers.
- When tens place flickers, push ZERO button once to change the LCD display value to "10.0".
Then, push ZERO+SPAN button.
- When units place flickers, push ZERO button 4 times to change the LCD display value to
"14.0". Then, until
“
SAVE" is displayed, push ZERO+SPAN button repeatedly.
- If
“
SAVE” is displayed, push SPAN Button to save set-up value.
-
Loop Test : Fix the 4~20mA Loop Current output to a certain value.
- Executing the menu to put ZERO+SPAN button.
- Moving to the sub directory to put Span button when 1 TRIM message appear.
- Moving to next menu to put Zero button when 11 Z-TRIM message appear.
- Moving to next menu to put Zero button when 12 Z-ADJ message appear.
- Executing Loop Test function to put Span button when 13 LOOP-T message appear.
- If Loop Test Function is performed, usable modes are indicated in the 2nd line of LCD, and
indication contents are as follows:
Indication
Content
Explanation
OFF
The current that corresponds to PV measured without using
Loop Test function is sent out