APT3500 Smart Pressure Transmitter
Operation Manual M3500-EO1G
31 DUON System Co., Ltd.
Engineering Unit.
- Letter input method is the same as numerical input method except “not only number but also
letter and partly special character can be enter into each DIGIT”. Hence, enter in the same
procedure as in (4) Zero Adjustment.
- Engineering Unit entered through button manipulation gives the same result as User Define
Unit under the communication environment of STT30 or HHT (Handheld Terminal).
-
Change Engineering Unit
- Executing the menu to put Zero+Span button.
- Moving to the next menu to put Zero button when 1 TRIM message appear.
- Moving to the next menu to put Zero button when 2 Setup message appear.
- Moving to the sub directory to put Span button when 3 LCD message appear.
- Moving to the next menu to put Zero button when 31 LCD-MD message appear.
- Moving to the next menu to put Zero button when 32 DEC-PL message appear.
- Moving to the sub directory to put Span button when 33 ENG-MD message appear.
- Moving to the next menu to put Zero button when 331 EN-URV message appear.
- Moving to the next menu to put Zero button when 332 EN-LRV message appear.
- Moving to the next menu to put Zero button when 333 E-UNIT message appear.
- Executing the function to put Span button when 334 E-TRF message appear.
- Until the desired Transfer Function, either "LINEAR" or "SQRT", is displayed on the LCD lower
part, push ZERO button repeatedly.
- If the desired Transfer Function is displayed, push SPAN Button to complete set-up.
- If “SAVE” is displayed, push SPAN Button to save set-up value.
* This product can print out measured results in various ways on the LCD screen. LCD
Engineering Mode is the function that converts measured result to “numerical value with
different weight”and prints out on the LCD screen. LCD Engineering Mode sets up
Engineering Range separately, and maps measured result (0~100%) to Engineering
Range and prints out on LCD. For the measured value handling procedure in the LCD
Engineering Mode, refer to [Figure3-10]. It should be noticed that both Transfer Function
and ENG. Transfer Function cannot be simultaenously set up as SQRT.