ATT2100 TEMPERATURE TRANSMITTER
Operation Manual M2100-REV-G
12
[Note3] Installation
All wiring shall comply with local installation requirement.
The cable entry devices shall be of a certified flameproof type, suitable for conditions of
use.
[Note4] Operation
Wait one minute after power -disconnection, before opening the enclosure.
Take care not to generate mechanical spark when access to the instrument and peripheral
devices in hazardous location.
[Note5] Maintenance
and
Repair
The instrument modification or parts replacement by other than authorized representative
of DUON System is prohibited and will void KOSHA Flameproof.
2.8.2
KEMA / ATEX Certification
ATEX Certification number : KEMA08ATEXxxxx
CE 0344
II 2 G
Note 1. Model ATT2100 for potentially explosive atmosphere
Ex d IIC T6... T4
Operating Temperature : -20
℃
≤
T
amb
+60
C
T6 for process
≤
85
C;
T5 for process
≤
100
C;
T4 for process
≤
130
C;
Note 2. Electrical Data
Supply Voltage : 11.9 to 42 Vdc
Output Signal : 4 to 20 mA + HART
Note 3. Electrical Connection : 2 x 1/2-14NPT Female
Note 4. ATT2100 ATEX Certification is according to the below standards
EN 60079-0 : 2006
EN 60079-1 : 2007
Note 5. Installation
All wiring shall comply with local installation requirement.
The cable glands and blanking elements shall be of a certified flameproof type, suitable for
the condition of use and correctly installed. Also those devices should be endured at the
130
C.
Housing Ground must be followed to “local electrical codes”. The most efficient ground
procedure is to connect directly to the earth as least impedance.
How to Housing Ground:
* Internal Ground Connection: Internal ground connection screw is located in terminal in
housing, the screw can be identified as ground sign.
* External Ground Assembly: This is located in the right side of housing and identified as
ground sign. (For grounding use a cable lug)
When use tubing, Stopping boxes must be connected with the wall of housing directly.
Tubing is installed a minimum of 5 threads.
Sensor is to be threaded a minimum of 7 threads and prevented from turning by tightening
the housing rotation set screw.
Do not disassemble flameproof Joints but in an unavoidable case to disassemble it or need
the specification of flameproof Joints, contact the manufacturer before doing.