ATT2100 TEMPERATURE TRANSMITTER
Operation Manual M2100-REV-G
13
Note 6. Operation
WARNING-DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Take care not to generate mechanical spark when access to the instrument and peripheral
devices in hazardous location.
Note 7. Maintenance and Repair
The instrument modification or parts replacement by other than authorized representative
of DUON System is prohibited and will void KEMA/ATEX Explosion-proof / Flame-proof.
2-8-3. FM Certification
HAZARDOUS LOCATION ELECTRICAL EQUIPMENT
ATT2100-abcd. Temperature Transmitters.
XP/I/1/ABCD/T6 Ta = 60
℃
;
DIP/II, III/1/EFG/T6 Ta = 60
℃
;
a = Transmitter Type : S, D
b = Electrical Connection : 1
c = Hazardous Location Certification : F1.
d = Option : BA, BF, C7, M1, X
Equipment Rating :
Explosionproof for use in Class I, Division 1, Groups A, B, C and D;
Dust-Ignition proof for Class II, Division 1, Groups E, F and G;
Dust-ignition proof for Class II, Division 1
“T6, see instruction for temperature code if process temperature above 85
℃
”
Ambient Temperature : -20 to 60
℃
Enclosure : indoors and outdoors, NEMA Type 4X
Conduit seal required within 18
”
for Group A only.
Nonincensive for Class I, Division 2, Groups A, B, C and D ; Class II, Division 2,
Groups E, F and G ; Class III, Division 1, Temperature Code T4
Ambient Temperature : -20 to 60
℃
Enclosure : indoors and outdoors, NEMA Type 4X
2.9 EMC Conformity Standards
EMI (Emission):
EN55011
EMS (Immunity):
EN50082-2
DUON System recommends customer to apply the Metal Conduit Wiring or to upset he twisted pair
Shield Cable for signal wiring to conform the requirement of EMC Regulation, when customer installs
AUTROL Series Transmitters to the plant.
Chapter 3 Transmitter Functions
3.1 Overview
This Chapter contains information on operating Model ATT2100. Tasks that should be performed on the
bench priori to installation are explained in this chapter.