ATT2100 TEMPERATURE TRANSMITTER
Operation Manual M2100-REV-G
23
3.10 Shop Commissioning using HHT
Commissioning consists of testing the transmitter, testing the loop, and verifying transmitter
configuration data. APT-3100 Pressure Transmitter may be commissioned using HHT of HART supported
either before of after installation.
▲
If you connect "TEST" pin, it's not communicated. If it doesn't exposed electronics circuits after install,
you must connect all Jumper of transmitter in the shop commissioning level. Analog output of transmitter
is 4~20 mA, thus it requires Power Supply at 11.9 V ~ 45 Vdc(ATEX:11.9 to 42Vdc) and Ampere meter
for measuring output current. You must connect 250~550 ohm resistor in Power Loop for HART
Communication and HHT or PC Configurator.
Figure 3-6 Connection the transmitter to HHT