ATT2100 TEMPERATURE TRANSMITTER
Operation Manual M2100-REV-G
38
4.13 Temperature Sensor Installation
NOTE
1. Install per local installation codes. Qualified cable entry or stopping box required.
(For Using ATEX explosion proof certificate, Must be use ATEX approved cable entry)
2. Temperature sensor assembly must be qualified for appropriate area classification.
(For Using ATEX explosion proof certificate, Must be use ATEX approved Temperature sensor)
3. Threads must be assembled with loctite thread sealant and have a minimum of five full threads
engagement and 8mm axial length engagement.
4. Must use qualified temperature sensor.
(For Using ATEX explosion proof certificate, Must be use ATEX approved Temperature sensor)
5. It is possible to install temperature sensor both side of housing and bottom of housing considering
the installation condition.
6. In the case of detecting high temperature (
T6: above 75
℃
, T5: above 90
℃
, T4: above 125
℃
)
,
use the remote type temperature sensor to prevent the influence to transmitter.