ATT2100 TEMPERATURE TRANSMITTER
Operation Manual M2100-REV-G
42
5.4 Check Output
Before other handle transmitter to on-line, you must examine and confirm whether transmitter
currently operate and suitably configure progress variable.
5.4.1 Process Variable
We use two progress variable in ATT-2100 SMART Pressure Transmitter pressure value is Primary
Variable and temperature value of pressure value configure SV(Secondary Variable) with fixed value.
Moreover this PV value ouputs with 4~20mA analog value.
5.5 Basic Setup
You must configure correlation variable for operating currently transmitter.
5.5.1 Select Sensor Range
Temperature range to measure is depended Range Code of sensor. This value is classified from
Temperature sensor module automatically.
5.5.2 Set Output Units
Select from the following engineering units:
Unit:
°
C,
°
F,
°
R,
°
K, etc
5.5.3 Rerange
Set the Zero and Span of 4~20mA analog output.
5.6 Detailed Setup
5.6.1 Set Fail Mode
When sensor is wrong or microprocessor of transmitter doesn't operate normally in order to outputs
current value of High or Low.
5.6.2 Set Damping Time
The sensor input value changes the response time of the transmitter to smooth variations in output
readings caused by rapid changes in input. Determine the appropriate damping setting based on the
necessary response time, signal stability, and other requirements of the loop dynamics of your
system. The default damping value is 1.0 seconds, and can be reset to damping values between 0
and 60 seconds.