background image

 

AC FAIL CIRCUIT 

 

Red LED indication on front panel

.

 

 

Relay contacts for AC fail “Normally open” or “Normally closed”.

 

 
GENERAL APPLICATION NOTES and WARNINGS 

 
WARNING: THERE ARE NO USER SERVICEABLE PARTS INSIDE.  HAZARDOUS VOLTAGES EXIST INSIDE THE UNIT.  SERVICE AND REPAIR 
MUST BE REFERRED TO QUALIFIED FACTORY PERSONNEL. 
 
NOTE: 

The individual user should take care to determine, prior to use or installation, whether this device is suitable, adequate or safe for the use 

intended.  Since individual applications are subject to great variation, DuraComm makes no representation or warranty as to the merchantability, 
suitability or fitness of these units for any specific application. 
 

NOTE: 

The precision regulated power supplies operate internally from voltages in excess of 12/24/48 volts.  In rare cases, voltage spikes or transients 

on the AC power line, or over heating, may cause a component failure in the power supply. Overloading the output will cause the over current feature to 
operate.  In either case, the cause must be determined and corrected. 

Failures require investigation as to cause and/or repair of the unit

 
INSTALLER NOTES 

 

NOTE:

 The outputs are NOT referenced to the chassis.  The Modular System can be used either positive or negative ground.  

 

NOTE:  DO NOT

 block any of the cooling vents on the sides or top and always allow adequate ventilation by not installing the unit inside tightly closed 

spaces.  Physical mounting position is not critical but the cooling vents and the internal thermostatically controlled cooling fans must not be blocked. 
 
 

RU2-3012-UPS wiring layout

 

 
This system setup will provide continuous power to the load while AC power is on. There is a seamless transfer of the load to the battery when the AC 
power goes off. The LVD will disconnect the battery if the voltage drops below 11.5 VDC. The battery reconnects once AC power is restored and voltage 
reaches 12.5 VDC. 
 

 

 

Recommended Copper Wire Size for Current Capacity 

(Insulated Wire, Single Conductor in free air) 

Current Level in Amperes 

 <7 AMPERES 

Wire Size 

20 AWG Up to 5 feet 
18 AWG Up to 10 feet 

 14  AMPERES 

18 AWG Up to 5 feet 
16 AWG Up to 10 feet 

 20  AMPERES 

16 AWG Up to 5 feet 
14 AWG Up to 10 feet 

 30  AMPERES 

14 AWG Up to 5 feet 
12 AWG Up to 10 feet 

 40  AMPERES 

12 AWG Up to 5 feet 
10 AWG Up to 10 feet 

 50  AMPERES 

10 AWG Up to 5 feet 
 8  AWG Up to 10 feet 

 70  AMPERES 

8 AWG Up to 5 feet 
6 AWG Up to 10 feet 

 100 AMPERES 

6 AWG Up to 5 feet 

RU2-3012-UPS 

Load 

NO COM  NC 

AC Fail 

NO=Normally Open 
NC=Normally Closed 
COM=Common 