3.13.6.1 ELECTRICAL DATA – WITH ELECTRIC HEAT: DRAH1T - continued
7.2/9.6 3/60
3-3.2
MULTIPLE CKT 1
20.0/23.1
4.6
31/35
35/35
RXBH-24A20C
7.2/9.6 3/60
3-3.2
MULTIPLE CKT 2
20.0/23.1
0
25/29
25/30
6021AS
RXBH-24A25C*
18.0/24.0 3/60
6-4.0
SINGLE
50.0/57.8
4.6
69/78
70/80
6024AS
9.0/12.0 3/60
3-4.0
MULTIPLE CKT 1
25.0/28.9
4.6
37/42
40/45
(208/240V)
RXBH-24A25C
9.0/12.0 3/60
3-4.0
MULTIPLE CKT 2
25.0/28.9
0
32/37
35/40
RXBH-24A30C*
21.6/28.8 3/60
6-4.8
SINGLE
60.0/69.4
4.6
81/93
90/100
RXBH-24A30C
10.8/14.4 3/60
3-4.8
MULTIPLE CKT 1
30.0/34.7
4.6
44/50
45/50
(6024S only)
10.8/14.4 3/60
3-4.8
MULTIPLE CKT 2
30.0/34.7
0
38/44
40/45
? Heater Kit Connection Type A=Breaker B=Terminal Block C=Disconnect Pullout
➀
D Voltage = 480 Volts
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater watts + motor watts) × 3.412 (see airflow table for motor watts.)
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Motor load is included in single circuit or circuit 1 of multiple circuits.
• Heater loads are balanced on 3 phase models with 3 or 6 heating elements only.
• Electric heater kits are not permitted for use with 115 volt air-handlers (A voltage).
• J Voltage (208/240V) single phase air-handlers are designed to be used with single or three phase 208/240V electric heaters. To connect 3
phase power to the air handler terminal block, bring only two leads to terminal block, cap, insulate, and fully secure the third lead.
• Do not install 480V electric heaters in 208/240V air-handlers.
• Do not install 208/240V electric heaters in 480V air-handlers.
• If the heater kit is listed under both single and multiple circuits, the heater kit is shipped from factory as multiple circuits. For single phase appli-
cations, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. See Section 6.2 for details.
AIR HANDLER
MODEL
DRAH1T
HEATER
MODEL
NO.
HEATER
KW
(208/240V)
(480V)
➀
PH/HZ
NO.
ELEMENTS
- KW PER
TYPE SUPPLY
CIRCUIT
SINGLE CIRCUIT
MULTIPLE CIRCUIT
HEATER
AMPS
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTION