background image

17

SUPPORTS

PLATE AND WALL SUPPORT

Ventilated Anchor Plate (APV)
Anchor Supports are designed to provide support to vertical sections

and provide fixed-point support for horizontal sections. See Figure 29.

NOTE:

 Rings installed at 90° to plates.

Figure 29: - Ventilated Anchor  Plate for Combustible material

The Plate Support must be attached to the building structure or supported 

with rigid structural members. See Table 3 for maximum supported height.

For maximum support, the entire perimeter of the Plate Support must be 

attached to structural framing. Structural members are supplied by the 

installer. See Figure 30 and 31.

Figure 30: - Ventilated Anchor Plate on a Framework

Figure 31: Detail of the Ventilated Anchor Plate on a Framework.

Supported duct sections in a vertical position must be braced with 

diagonal members or gussets to prevent deflection of the supported joint 

as shown in Figure 31. ”X” is a minimum of 30°.

Plate Supports are usually located adjacent to fittings, such as tees or

elbows, to protect fitting from expansion stresses. Table 8 shows Plate 

Support, bracing and framework requirements for duct size ranges.

NOTE:

 If bracing is used, minimum “X” angle is 30°. If there is no

  bracing, the framework must be attached to structural members  

to provide equivalent rigidity.

Figure 32: - Anchor Plate Horizontal Bracing

Summary of Contents for DAS1

Page 1: ...stallation Follow these instructions exactly as written Check severeness of joints upon completion of assembly C This venting system must be free to expand and contract This venting system must be sup...

Page 2: ...TION FOR ALL MODEL DAS1 BC INTRODUCTION DAS1 BC double wall 5 TO 36 is a special stainless steel vent system for gas fired appliances listed as Category I II III and IV in USA UL 1738 or in Canada asT...

Page 3: ...in accordance with their respective instructions These parts which are installed in contact with wood or other combustibles are designed and tested to assure that they do not overheat at points of co...

Page 4: ...are designed for multiple venting Cat II III or IV appliances MAY NOT be common vented with Cat I natural draft appliances This limitation can be removed if an engineering analysis demonstrates norma...

Page 5: ...nchorPlate AP Fornon combustibleapplicationonly 5to 22 133 24to 36 82 AnchorPlatewithLength APL Fornon combustibleapplicationonly 5to 22 142 24to 36 87 AnchorPlateVentilated APV 5to 22 133 24to 36 82...

Page 6: ...t of more than 10 feet the stack must be supported by a Guy Section 3 TheventsystemmustterminatewithoneoftheDAS1 BC terminations Except a Category I appliances natural draft must use a Rain Cap It is...

Page 7: ...WallThimble WT WTI Air gap or insulated Two half plate Termination Add sealant Opening dimension Table 5 for opening for all Models 2 Minimum overlap WALL PENETRATION 1 Prior to installation determin...

Page 8: ...t of the appliance 1 ADrainlength DL oraTeewithadrainteecap DTC isstronglyrecom mended Installthisdrainascloseaspossibletotheappliancefluecollar 2 A condensate drain is required for every 30 feet of h...

Page 9: ...8 LATERAL TEE BT88 DRAIN TEE CAP DTC DRAIN LINE By Others Trap Heigth must be equal to max appliance outlet Pressure Finishing Cone FC zzzz zzzzp z z z z zzzz frZZ ZZ 2j lZ ZZ ZZ zzzzzz V FIXED SUPPOR...

Page 10: ...s the value In theTable 7 8 use bracing or cable guying to stabilize chimney section above the roof See Figure 6 Figure 6 Height with rigid bracing or guying option for DAS1 BC Figure 7 Maximum freest...

Page 11: ...ring on the Centering Flue Extension STEP 2 for HORIZONTAL installation only Only on Horizontal installation add a bead of blackViton caulking over the Viton O ring NOTE Sealant Caulking is supplied...

Page 12: ...to the inside of the inner flue adjacent to the nipple to channel the effluent to the drain 3 The duct drain is intended for use at the end of a horizontal run where access and drainage is needed see...

Page 13: ...he unflanged end of the tube should always point downward or towards downward slope Figure 12 Overlap Details forVariable Length INSTALLATION STEPS FORTHEVARIABLE LENGTH LV Step 1 Measure the distance...

Page 14: ...regular length installation See JOINT ASSEMBLY section Step 8 Apply thin layer of sealant inside the retaining collar and also a continuous bead of sealant at the collar overlap seam See Figure 17 Fi...

Page 15: ...be connected to a suitable disposable point It can also be used as an access for clean outs or access purposes See Figure 23 Same installation as aTee Cap TC ELBOWS ELBOWS E2 El5 E30 E43 E45 E88 E90...

Page 16: ...is used for a diameter change in duct system Uses when there is a sufficient length for duct run available for the size change TheTIN0 is used uses 2 of length per 1 increment diameter change TheTIN0...

Page 17: ...members are supplied by the installer See Figure 30 and 31 Figure 30 Ventilated Anchor Plate on a Framework Figure 31 Detail of theVentilated Anchor Plate on a Framework Supported duct sections in a v...

Page 18: ...art See Figure 34 35 36 for the three steps to install the DAS1 BC Figure 33 Ventilated Anchor Plate with Length APVL Figure 34 Step 1 of installation of APVL Figure 35 Step 2 of installation of APVL...

Page 19: ...crews of the flange band The Heavy DutyWall Support Assembly is bolted together with provided hardware It is made with adjustable struts which allows a variable clearance from the non combustible wall...

Page 20: ...hardware provided to form a rigid assembly NOTE Seal joint with S 375 sealant above and below support if exposed to weather Can be attached to combustible wall FULL ANGLE RING FAR A Full Angle Ring i...

Page 21: ...rtical position The inlet and outlet ends must each be supported TEE SUPPORT TheTees must be supported properly to protect them from bending It can be done by means of Anchor Plate AP Anchor Plate wit...

Page 22: ...ch 5 to 30 See Figure 49 Figure 47 Storm Collar Figure 48 Flashing Figure 49 Adjustable Flashing NOTE The flashings are non ventilated and does not provide for any reduced clearance to combustible INS...

Page 23: ...incorporates a drain hose from either a Drain length or a Drain tee cap the hose must be inspected periodically to ensure that water is in the trap loop If a proper trap loop is not maintained exhaus...

Page 24: ...08 08 19 DuraVent Limited reserves the right to make changes at any time without notice in design materials specifications prices Consult your local distributor for chimney system code information 10...

Reviews: