5

CHIMNEY  DIAMETER

Follow the fireplace manufacturer’s manual 

to determine required chimney diameter and 

clearances between combustible materials 

and your fireplace.  Never use a chimney 

with an inside diameter smaller than your 

flue opening above firebox unless specifically 

allowed by the fireplace manufacturer. If you 

are connecting to a masonry fireplace, refer to 

Table 2 (pg 11) for proper sizing.  To calculate 

the chimney’s outside diameter, add 3 inches 

to the inside diameter. 

CHIMNEY  HEIGHT 

The national Fire protection Association 

Standard #211 states: “Chimneys shall extend at 

least three feet above the highest point where it 

passes through the roof of a building, and at least 

two feet higher than any portion of a building 

within ten feet.” (Fig. 1).  Due to the overlap of 

the joints, subtract 1 inch from each Chimney 

Section’s height to calculate installed height.

CHIMNEY  ENCLOSURE  

REQUIREMENTS

 

Through Rooms:  Interior chimneys shall 

be enclosed where they extend through 

closets, storage areas, occupied spaces, or 

anywhere where the surface of the chimney 

could be contacted by persons or combustible 

materials (including insulation).  The air space 

between the outer wall of the chimney and the 

enclosure shall be at least 2 inches 

Multi-Story:  Consult local building code 

officials for requirements in your area. The 

national Fire protection Association Standard 

#211 states:  “Factory-built chimneys that 

pass through floors of buildings requiring 

the protection of vertical openings shall be 

enclosed with approved walls having a fire 

resistance rating of not less than one hour 

when such chimneys are located in a building 

less than 4 stories in height, and not less than 

2 hours when such chimneys are located in a 

building more than 4 stories in height.”

In Canada, except in single-family and two-

family dwellings, chimneys which extend 

through another story must have an enclosure 

with a fire resistance rating equal to or greater 

than that of the floor or roof assembly through 

which they pass. 

Cold Climates: In cold climates, chimneys 

mounted on an outside wall should be 

enclosed in a chase. exterior chases reduce 

condensation and creosote formation, and 

enhance draft. Always maintain a 2” air-space 

clearance to combustibles.

FIREPLACE  RECOMMENDATIONS

Always follow the fireplace manufacturer’s 

installation instructions.   

Installation:

 Install your fireplace as described 

by the fireplace manufacturer. Be sure to 

maintain all required clearances.

Flues:

 Connect only one fireplace per chimney.

Operation: Follow the fireplace safety manual 

for maximum efficiency and safety.  Do not over 

fire. Any damage to the fireplace or chimney can 

possibly void your warranties.  

Fuels:  Do not burn driftwood, plastic, or 

chemically treated wood such as railroad ties.  

They are corrosive to your chimney system.  

Follow the fireplace manufacturer’s instructions 

regarding fuels.

3 FOOT MINIMUM

ABOVE ROOFLINE

2 FOOT 

 ABOVE

 10 FOOT

HORIZONTAL

ANY POINT

WITHIN

Figure 1

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for DuraChimney II

Page 1: ...himney ii Complete Venting Solutions for the Hearth Industry Installation Instructions Air Cooled All Fuel Chimney for Fireplaces NorthlineExpress com http www northlineexpress com Toll Free 1 866 667...

Page 2: ...Chimney II is listed to UL 103 and ULC S604 standards for use on masonry fireplaces which burn wood oil coal or gas Some factory built fireplaces may be listed with DuraChimney II Check to the firepla...

Page 3: ...ce Installation Frame Opening Chart 6 Chimney Sizing Chart 11 Elbow Offset Installation 13 Elbow Offset Chart 14 Chimney Maintenance 15 Warranty 16 Air cooled all fuel chimney for fireplaces DuraChimn...

Page 4: ...or positive pressure appliances The DuraChimney II system is designed to extend vertically with a maximum of one 1 offset two elbows total of up to 30 from vertical DuraChimney II is listed under UL R...

Page 5: ...rough floors of buildings requiring the protection of vertical openings shall be enclosed with approved walls having a fire resistance rating of not less than one hour when such chimneys are located i...

Page 6: ...on which to attach the Anchor Plate or Anchor Plate If the top of the masonry does not have a level surface then you will need to modify the masonry accordingly Center the Anchor Plate over the mason...

Page 7: ...ve cut Frame openings at each floor level above the Fireplace Fig 4 These openings are to hold the Firestop and Attic Insulation Shield Locate each opening by dropping a plumb bob to the four corners...

Page 8: ...ections Fig 6 Do not penetrate the inner liner of the chimney Use a Wall Strap every eight 8 feet of chimney height 9 Supplementary Support and Stabilizer Install a Supplementary Support if total chim...

Page 9: ...cannot fit or is not used you must enclose the attic portion of the chimney in a framed enclosure always maintain 2 air space clearance to combustibles If the chimney is fully enclosed through the at...

Page 10: ...g members are further away from the chimney than 2 center the Roof Radiation Shield to the chimney on the framing member and secure in place with screws or nails 12 Attach Flashing For chase enclosure...

Page 11: ...le is 12 diameter pipe T W H T W H 8 7 6 30 16 14 20 8 10 15 12 10 50 40 30 24 48 60 36 42 72 HEIGHT 36 30 42 24 48 18 W IDTH 18 20 22 24 20 18 60 72 84 84 HEIGHT FEET CHIMNEY FIREPLACE OPENING INCHES...

Page 12: ...he Flashing Fig 15 Slide the Storm Collar down over the chimney to the top of the Flashing The Storm Collar must be installed 1 off the Chase Top Flashing to provide proper ventilation Fig 15 Tighten...

Page 13: ...1 Attach Elbows Attach Elbow to Chimney Section or other Elbow by mating the male and female ends with each other and using the 4 sheet metal screws provided Attach one Elbow to the Chimney Section b...

Page 14: ...hes Rise Inches Offset Inches Rise Inches 15 0 2 20 2 21 2 21 2 21 15 12 5 31 5 31 5 32 5 32 15 18 7 37 7 37 7 38 7 36 15 36 11 54 11 55 11 55 11 55 15 48 14 66 14 66 14 67 14 67 30 0 5 22 6 22 6 24 6...

Page 15: ...attach the top lid of the Cap to the cap s legs 5 Coal To reduce corrosion in chimneys where coal is burned clean the chimney thoroughly within 48 hours of shutting down the appliance for the season 6...

Page 16: ...ro PelletVent CornVent DuraLiner DuraFlex DirectVent Pro Type B Gas Vent DuraConnect or DVL with dated proof of purchase Purchaser s sole remedy is replacement of component fittings and chimney pipe l...

Reviews: