background image

10

8.  Install Attic Insulation Shield:

  The 

Attic Insulation Shield is required where the 

chimney passes into an attic.  Its purpose is 

to prevent debris and insulation from getting 

too close to the chimney 

(Fig 10)

.  An installed 

Attic Insulation Shield is 15 inches high.  In 

attic areas where this shield cannot fit, you 

must enclose the attic portion of the chimney 

in a framed enclosure.  If the chimney is fully 

enclosed through the attic, an Attic Insulation 

Shield is not required.  If the chimney passes 

into the attic, install the Attic Insulation Shield 

as follows: 

a. 

 If the Firestop Radiation Shield extends 

above the attic floor, no modifications are 

necessary.  The Firestop Radiation Shield will 

fit inside the Attic Insulation Shield.  

b.

  Assemble Chimney Sections until at least 

18 inches of chimney extends above the 

Firestop Radiation Shield.

c.  Extend the Firestop Radiation Shield tube 

extension (keep at least 1” overlap), and 

secure in place using sheet metal screws.

d.  Slip the Attic Insulation Shield over the 

Chimney and Firestop Radiation Shield until 

the base sits squarely on the framed opening 

(Fig 7 & 10)

.

e.  Secure the Attic Insulation Shield to the 

top of the framed opening using at least (3) 

8-penny nails or (3) #8, 1-1/2” wood screws 

per side 

(Fig 10)

.  

f.

  Wrap the Collar of the Attic Insulation Shield 

around the chimney and fasten it loosely.  Slide 

the Collar down to meet the Attic Insulation 

Shield.  Slip the tab through the adjacent slot 

and fold it back to tighten and secure the 

Collar 

(Fig 11)

9.  Attach Flashing:

 In new construction, 

assemble the Chimney Sections to a point  

above the roof, then slip the Flashing over 

the chimney.  On an existing roof, center 

and install the Flashing before extending the 

Figure 11

Figure 12

Figure 13

ROOFING 

FASTENERS

ADJUSTABLE 

FLASHING

PUSH COLLAR 

DOWN TO 

FLASHING AND 

SEAL WITH NON-

HARDENING HIGH-

TEMP SILICONE 

SEALANT

7. Assemble Chimney Sections:

  Lower 

the female end of the first Chimney Section 

in the Support Box 

(Fig 9)

.  It will twist-lock 

clockwise onto the male end of the Support 

Box.  Turn Pipe Sections firmly clockwise to 

lock them together.  Sheet metal screws are 

not required, but they may be used to reinforce 

the connection, if desired.  Use only 1/2” (or 

shorter) sheet metal screws.  Do not penetrate 

the inner liner of the chimney.  

Summary of Contents for DuraTech Series

Page 1: ...DuraTech All Fuel Chimney System 5 to 8 diameter Installation Instructions...

Page 2: ...ep these instructions for future reference This booklet also contains instructions for installing a venting system within an existing masonry chimney and for installations passing through a cathedral...

Page 3: ...EP DIRECTIONS 6 CEILING SUPPORTED 7 OFFSET ELBOW INSTALLATION 11 EXTENDED ROOF BRACKET INSTALLATION 13 ROOF SUPPORTED INSTALLATIONS 13 TEE SUPPORTED INSTALLATIONS 16 MASONRY FIREPLACE INSTALLATIONS 21...

Page 4: ...actory built fireplaces check with your fireplace manufacturer Otherwise DuraTech has not been approved for use with solid fuel appliances in Canada DuraTech Chimney is available in 5 6 7 8 diameters...

Page 5: ...Shield Elbow with swivel Attic Insulation Shield Tee with Tee Cap Elbow Strap Adjustable Tee Support Bracket Adjustable Wall Strap Chimney Cap Anchor Plate Round Ceiling Support Box Extended Roof Bra...

Page 6: ...mation and enhance draft Include an access door by the Tee Cap for chimney cleaning Refer to Fig 23 STOVE RECOMMENDATIONS Follow the stove manufacturer s instructions The requirements stated below per...

Page 7: ...d Support Box the Flat Ceiling Support Box the Square Ceiling Support Box Reduced Clearance Support Box or the CAS Ceiling Support The CAS Ceiling Support is only used when installing the CAS system R...

Page 8: ...pport Box and secure them to the framing members using the 6 1 1 4 long round head wood screws provided see Fig 6 4 Frame Openings Frame openings in each ceiling or floor above the Support Box Fig 7 T...

Page 9: ...is on the ground floor Support Box is in the 1st floor ceiling you would need a Firestop Radiation Shield at the 2nd floor ceiling and at the 3rd floor ceiling etc including where the chimney penetra...

Page 10: ...ion Shield until the base sits squarely on the framed opening Fig 7 10 e Secure the Attic Insulation Shield to the top of the framed opening using at least 3 8 penny nails or 3 8 1 1 2 wood screws per...

Page 11: ...the cap and twist locking it clockwise onto the chimney Do not hold upper portion of the cap and twist as this may damage the cap The Chimney Cap can be removed for chimney cleaning as described in t...

Page 12: ...8 38 15 36 11 50 15 48 14 61 15 48 6 15 66 15 48 12 17 72 15 48 18 18 78 15 48 24 20 83 30 0 4 15 30 6 6 30 12 9 25 30 18 12 30 30 24 15 35 30 36 21 46 30 48 27 56 30 48 6 29 60 30 48 12 32 65 30 48 1...

Page 13: ...bottom halves of the Adjustable Leg In order to secure Legs in proper position there is a hole provided in the outer leg where the outer and inner halves overlap Use a 1 4 drill bit to drill through...

Page 14: ...install the remainder of the Combustible Air System The Support Box must remain level and the top edge of the box must cover the edge of the roof s decking material Square Ceiling Support Boxes are a...

Page 15: ...im sections into the ceiling Fig 6 4 Complete Installation Refer to Steps 7 9 10 in the Ceiling Supported Installation section to complete the Roof Supported installation Figure 20 Figure 21 2 A Roof...

Page 16: ...ers Please note that you cannot extend the chimney all the way to the appliance you must have some connector pipe 1 Cut and frame opening to provide a minimum of 2 clearance on all sides of the chimne...

Page 17: ...uter walls at this location Refer to Table 2 for the appropriate framing dimensions 3 Install Wall Thimble The Wall Thimble is two piece component which includes the Interior half and the Exterior hal...

Page 18: ...ust for desired clearance to wall and secure by tightening bolts Figs 26 27 5 Install Tee and Cleanout Chimney Figure 25 Figure 26 INSTALLATION WITH TEE BELOW TEE SUPPORT SHOWN WITH LEG BRACKETS MOUNT...

Page 19: ...on to the female end of the Chimney Branch by twisting clockwise 8 Complete Chimney Attach the Chimney Sections as in Step 7 in the Ceiling Supported Installation section Secure the chimney to the wa...

Page 20: ...e the Chase Top Flashing Spacers to allow the proper air gap clearances on the galvanized sheet The Chase Top Flashing Spacers are available to insure that the proper air gap is maintained Figure 29 d...

Page 21: ...th a high temperature 1000 F sealant Secure Anchor Plate with at least 4 1 4 x 4 masonry anchors Fig 30 It is very important that the Anchor Plate is level Be sure to maintain a 1 min clearance to com...

Page 22: ...he Slip Connector or Snap LockAdapter slips into the opening in the Ceiling Support or Finishing Collar Align the tabs on the Slip Connector or Snap LockAdapter with the notches in the face of the Sup...

Page 23: ...sk of chimney fire 4 How to Clean Have your chimney cleaned by a Certified Chimney Sweep if you have doubts about your ability to clean it Use a plastic wood or steel brush Do not use a brush that wil...

Page 24: ...Sweep orVENTINOX installer The Liner and Components warranty is further subject to compliance with the following requirements throughout the warranty period The chimney must have a chimney cap and che...

Reviews: