600
600
2250*
0
1
2
L
N
PE
II
I
76xxxx xx x xx xx00: 50 Hz, 220 - 240 V AC
76xxxx xx x xx xx06: 60 Hz, 220 - 240 V AC
I
N
= 16 A
I
∆
N
≤
30 mA
Power supply
Fuse protection
RCD
* or the height of
the highest shower
head / water outlet
that is permanently
installed; depending
on which is higher
Safety areas in accordance with DIN VDE 0100-701
16
Connecting the whirltub (Diagram 16)
NOTE!
Avoiding any malfunctions!
λϡ
Do not fasten the cables together with cable ties.
λϡ
Do not install the supply line parallel to the control
cables.
I
Connect the supply line to the mains supply socket.
II
Connect the potential equalisation cable to the
whirltub.
Pre-installation
> Installing a permanent power supply line:
λϡ
Pre-connect a separate fuse and residual current
operating device (RCD)
λϡ
Pre-connect an all-pole separating main switch
outside the prescribed safety areas (0 - 2)
λϡ
Allow the supply line to protrude by 3,000 mm
> Laying the potential equalisation cable:
λϡ
Allow the cable to protrude by 3,000 mm
Electrical installation
WH_M_Einbau_WV_Magnete/15.12.7
7