Electrical installation
Water installation
Position of electrical / water connection
60 60
325
IG 1/2”
Pre-installation
>
Lay a permanent power supply line:
λϡ
Please observe the position of the electrical connec-
tion
λϡ
Leave at least 800 mm of feed cable exposed
>
Install circuit breaker
λϡ
Connect a separate upstream circuit breaker
λϡ
Connect an upstream residual current device (RCCB)
separating all poles
18
Connecting the cable (Diagram 18)
>
Please observe the L, N and PE conductors.
20
Installing junction box (Diagram 20)
>
Fix the junction box in the floor-standing toilet in
the designated place.
Power supply
220 – 240 V ~ 50/60 Hz
Max. rated power
1.65 kW
Circuit breaker
I
N
= 16 A
RCCB
I
N
= 30 mA
Protection type
IP X4
Protection class
1
Cold water
DN 15 (1/2")
Water pressure
0.07 - 0.75 MPa
(0.7 - 7.5 bar)
Water hardness
max. 2,4 mmol/l
NOTE!
>
Install a water water softener with water
hardness ≥ 2.4 mmol/l (≥ 14° dH and/or
24° fH).
Pre-installation
>
Install the water connection and water outlet in the
specified areas.
DANGER!
Health risk and potential product damage.
>
Supply the Shower WC with cold drinking water from the
main water system.
>
Do not connect any waste water, grey water, industrial
water, sea water or other untreated or semi-treated
water.
7
Connecting the water (Diagram 7)
NOTE! Avoiding any malfunctions!
>
Only use the water supply hoses provided.
9
Connecting the water (Diagram 9)
NOTE! Avoiding any malfunctions!
>
Only use the water supply hoses provided.
SensoWash_MAL_SWC_54025/14.05.4
7
en