4.3
Quattro Tandem
Electrical data
4642-54
4682-54
4682100001
Rated voltage
V
400
400
Mains frequency
Hz
50
60
50
60
Nominal current at 8 bar (0.8 MPa)
A
4.4
4.8
8.8
9.6
Type of protection
IP 21
IP 21
Mains fuses *
A
16
16
Max. permissible mains impedance in
accordance with EN 61000
‑
3
‑
11 **
W
£
0.24
£
0.18
*
Circuit breaker fuse characteristics B, C or D in acc. with EN 60898-1
**
Mains impedance at 6 switching cycles per hour. If the number of switching cycles per hour is
higher a lower mains impedance is required.
General technical data
Pressure tank volume
l
90
90
Suction power, approx.
l/min
420
505
845
1010
Delivery at 5 bar (0.5 MPa)*
l/min
258
293
516
586
Pressure build-up phase 0 - 7.5 bar (0 -
0.75 MPa) c.
s
180
160
90
80
Duty cycle
%
100
100
Start-up pressure
bar (MPa)
5.5 (0.55)
5.5 (0.55)
Cut-off pressure
bar (MPa)
7.5 (0.75)
7.5 (0.75)
Cut-off pressure, max. adjustable
bar (MPa)
9.0 (0.9)
9.0 (0.9)
Safety valve, maximum permissible oper-
ating pressure
bar (MPa)
10 (1)
10 (1)
Pressure dew point at 7 bar (0.7 MPa)**
°C
£
+5
£
+5
Dimensions (H x W x D) ***
cm
82 x 102 x 62
82 x 102 x 62
Weight
kg
120
170
Noise level ****
dB(A)
69
70
72
73
*
Delivery without membrane drying unit, at +20°C and 1013 mbar (0.1 MPa)
*
Value determined at an ambient temperature of +40 °C
**
Values without accessories and add-on parts
****
Noise level in accordance with ISO 3744
Filter mesh size
Air intake filter
µm
3
Fine filter
µm
3
Virus bacteria filter
µm
0.01
Sinter filter
µm
35
Coalescence filter
µm
0.01
Product description
12
4252100034L02 2105V002