BIO-FIGHTER® ULTRA-FLEX INSTALLATION & OPERATION MANUAL
2
Dimensions
Chassis: 9.25"L x 4"W x 2 "H
Lamp Housing: 3.6"L x 3"W x 1.25"H
Lamp Bracket: 3.25"L x 3"W x 4"H
Weight:
Approx. 4 lbs.
Electrical
:
120V-240V, 50/60Hz, 1PH. 3 amp-250V fuse.
6 ft. power cord.
U.S. Patent Nos. 5,334,347, 5,817,276, 6,245,293, 6,267,924,
6,280,686, 6,313,470, 6,627,000, 6,539,727, 6,932,494, 6,550,257.
Specifications subject to change without notice.
UV-C Light May Degrade Plastic and Rubber.
Shield exposed plastic drain pans, wire insula-
tion, flex duct, or other plastic/rubber compo-
nents from UV-C light.
REMOTE LAMP MOUNTING LOCATION
Select a mounting location with enough clear-
ance for the lamp to be installed and replaced
easily. Allow a 1" clearance between duct sur-
face and lamp tip.
A 120V or 240V electrical supply is required.
CAUTION
Special Installation Notes
• Do not install in closet return grille applications.
• Do not install in outdoor applications.
• Do not expose wiring or plastic parts to UV-C light.
• Do not install where UV-C light can be seen
after installation.
• Do not install beneath a humidifier.
• If the UV device is installed on the inlet side
(return air side) of a coil, make sure that the
HVAC system is configured such that the
blower is located between the return air filter
and the inlet side (return air side) of the coil,
such as would be found in a traditional up-
flow, or horizontal furnace with the coil
placed after the heat exchanger.
• If the UV device is installed near an air filter,
check with filter manufacturer for UV-C
resistance properties.
• If the desired UV installation location is
intended to irradiate an air filter, to neutralize
the microbiological matter on the air filter
surface, such as would be found in the
return air drop of a basement application or
in the return plenum of a horizontal system
in an attic; take precautions as described in
note above, and make sure the UV fixture is
placed on the return side of the filter. DO
NOT INSTALL THE UV FIXTURE ON EITHER
SIDE OF THE FILTER IN HALL / CLOSET
RETURN AIR APPLICATIONS.
(See ATTEN-
TION! Warning sheet #212945-00).
250V/3 Amp Fuse Only
ON
OFF
9.25"
2"
4"
Remote Lamp Housing
3.6"
1.25"
3"
ETL LISTED
CONFORMS TO
UL STD 1598
CERTIFIED TO
CSA STD C22.2 NO. 250.0
2002554
EPA Device Manufacturer Establishment No. 73316-TX-1
The product and technologies described are not medical devices, and are
not intended to diagnose, treat, cure, or prevent any disease or illness.