Getting Started
Seting printer, as well as look of RMO Test Report where given at figures below.
6.8 Duty Cycles
During tests, RMO200 generates a high DC current that heats up the test set. To
prevent RMO200 from overheating, certain duty cycles apply depending on the
used test current.
S i n g l e T e s t
Test current
(A)
Cooling time between
first 4 tests (sec)
Cooling time after
4 tests (sec)
5, 10, 20
50, 100
0
150, 200
0
10
C o n t i n u o u s T e s t
Test current
(A)
Maximal test
duration
time (sec)
Cooling time
between tests (sec)
5,10,20
50, 100
300 0
150, 200
150
300
A built-in control prevents these cooling times from being skipped. If you try to
start a test within the cooling period, the display shows "Wait" and a timer
counting down. After the cooling period has elapsed, start the test using the set
test parameters by pressing the
Ω
button. Cooling of RMO200 is supported by
a built-in fan that is automatically activated every time a test is started from the
Test
menu. It continues running 5 minutes after the test is finished.
Table 6-11:
Cooling time
between
single
tests
Table 6-12:
Cooling time
between
continuous
tests