background image

Series CDTA Communicating Carbon Dioxide Detector

Specifications - Installation and Operating Instructions

Bulletin AQ-CDTA-QS

The 

Series CDTA Communicating Carbon Dioxide Detector 

combines the function 

of three room sensors into a single, compact housing. Parameters include carbon 

dioxide, humidity, temperature, and temperature set point with override. By having 

field selectable Modbus® and BACnet Communications, only four wires are needed 

for power and the communication signal. The communicating detectors can be daisy-

chained together to further reduce installation cost. In order to reduce the set up time, 

the RS-485 MAC  address is set up using on board dip switches. A second set of 

dip switches are used to select whether output is Modbus® RTU or BACnet MS/TP 

communication protocols and to limit access to the set up menu.

Like  our  Series  CDT  Carbon  Dioxide  Transmitter,  the  Series  CDTA  uses  a  Single 

Beam Dual Wavelength Non-Dispersive Infrared (NDIR) sensor to measure the carbon 

dioxide level. This technology can be used in installations that will be occupied 24 

hours per day.  For improved accuracy, the transmitter can be field calibrated to the 

environmental  conditions  of  the  installation.  Also,  the  barometric  pressure  can  be 

programmed to correct for altitude. The humidity uses a capacitive polymer sensor and 

the temperature is measured using a 10KΩ thermistor sensor. The humidity sensor is 

field replaceable without the need for additional calibration.

Optional local and remote displays are available to display any of the parameters. For 

applications in which the building occupants aren’t familiar with CO

2

 concentrations, 

the  LCD  can  be  programmed  to  display  temperature,  humidity,  or  temperature  set 

point instead.

Installation

SPECIFICATIONS

Sensor (CO

2

):

 Single-beam, dual-wavelength NDIR; Humidity: Capacitive polymer; 

Temperature: Solid state band gap.

Range:

 CO

2

: 0 to 2000 or 5000 PPM CO

2

 (depending on model); Humidity: 0 to 

100% RH; Temperature: 32 to 122°F (0 to 50°C).

Accuracy:

 CO

2

: ±40 ppm ±3% of reading; RH: ±2% (10 to 90% RH); Temperature: 

±1°C @ 25°C.

Temperature Dependence (CO

2

):

 ±8 ppm / °C at 1100 ppm.

Non-Linearity (CO

2

):

 16 ppm.

Pressure Dependence (CO

2

):

 0.13% of reading per mm of Hg.

Response Time (CO

2

):

 2 minutes for 99% step change.

Temperature Limits:

 32 to 122°F (0 to 50°C).

Humidity Limits:

 10 to 95% RH (non-condensing).

Power Requirements:

 10 to 42 VDC / 10 to 30 VAC.

Power Consumption:

 Average: 0.5 watts; Peak: 1.2 watts.

Output:

 2-wire RS-485, Modbus

®

 RTU or BACnet MS/TP communication protocol.

Weight:

 4.4 oz (125 g).

Agency Approvals:

 BTL, CE.

European style

North American style

1.08

[27.33]

1.10

[27.96]

4.50

[114.30]

2.80

[71.12]

3.65

[92.72]

3.56

[90.42]

Use electrostatic discharge precautions (e.g., use of wrist straps) 

during installation and wiring to prevent equipment damage.

For optimal performance, self calibration feature of the transmitter 

requires exposure to normal outdoor equivalent carbon dioxide 

level once every thirty days.

Avoid  locations  where  severe  shock  or  vibration,  excessive 

moisture or corrosive fumes are present.

Do  not  exceed  ratings  of  this  device,  permanent  damage  not 

covered by warranty may result.

Upon powering the transmitter, the firmware version will flash on 

the  display. A  warm  up  period  of  30  minutes  is  required  for  the 

transmitter to adjust to the current CO

2

 concentration.

NOTICE

NOTICE

NOTICE

NOTICE

NOTICE

Disconnect power supply before installation to prevent electrical 

shock and equipment damage.

 

Make  sure  all  connections  are  in  accordance  with  the  job  wiring  diagram  and  in 

accordance with national and local electrical codes. Use copper conductors only.

CAUTION

Modbus

®

 is a registered trademark of Schneider Automation, Inc.

®

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com
e-mail: info@dwyermail.com

Summary of Contents for CDTA-2E000

Page 1: ...ength NDIR Humidity Capacitive polymer Temperature Solid state band gap Range CO2 0 to 2000 or 5000 PPM CO2 depending on model Humidity 0 to 100 RH Temperature 32 to 122 F 0 to 50 C Accuracy CO2 40 ppm 3 of reading RH 2 10 to 90 RH Temperature 1 C 25 C Temperature Dependence CO2 8 ppm C at 1100 ppm Non Linearity CO2 16 ppm Pressure Dependence CO2 0 13 of reading per mm of Hg Response Time CO2 2 mi...

Page 2: ... two 6 M2C type screws provided 4 Pull wires through sub base hole and make necessary connections 5 Reattach cover to base plate WIRING Figure 2 shows how to connect the CDTA in a network containing a common power supply Use a cable containing two twisted pairs One pair is to be used for B and A The other pair is to be used for power and common This configuration is not suitable for AC supplies Us...

Page 3: ...oint temperature will be set to the new set point low limit temperature Set Point High Limit Temperature SOH This value sets an upper limit on the current set point value The set point high limit value is numerical setting that supports continuous change increment decrement by press and holding of either UP or DOWN button If the new set point high limit temperature is lower than the current set po...

Page 4: ...e vertical plane as shown in Figure 5 Step 5 Follow the steps in the accessing parameter section to access the calibration parameter CAL Step 6 Press and hold the Up and Down arrows for 3 seconds Step 7 Flow zero reference gas at 0 3 SLPM for 5 minutes Step 8 Press and hold the Down button for 0 5 seconds Step 9 Flow the full scale reference gas at 0 3 SLPM for 5 minutes Step 10 Press and hold the...

Reviews: