The Series CFS2 Cable Float Switch

is a mechanically actuated floating switch

intended to activate electrical components, usually pumps, to start and stop
automatically. The CFS2 is perfect for simple level control of liquids for filling or
draining reservoirs and tanks. Float switches such as the CFS2 are the most
universally used for pump automation due to their high reliability, economical
pricing, and easy installation. Counterweights and cable hangers are available to
suit a variety of mounting applications. Optional cables available include those with
UL/CSA approval, higher chemical compatibility, high temperature durability, oil
resistance, and drinking water suitability. Contact factory for piggyback plug option,
gold contact switch option and cable length options ranging from 10 to 70 ft (3.04
to 21.34 m).

Series CFS2 Cable Float Switch

Specifications - Installation and Operating Instructions

Bulletin L-CFS2

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. 

Fax: 219/872-9057

e-mail: info@dwyer-inst.com

SPECIFICATIONS
Service: 

Compatible liquids.

Wetted Materials: 

Housing: Polypropylene; 
Cable: CFS2-XXPXX-XX: PVC;

CFS2-XXNXX-XX: Neoprene;
CFS2-XXSXX-XX: 3x16 AWG SJOW;
CFS2-XXTXX-XX: Rubber compound EM7 quality  ;
CFS2-XXWXX-XX: EPDM ethylene propylene.

Temperature Limits: 

32 to 122°F (0 to 50°C).

Pressure Limits: 

14.5 psi (1 bar).

Enclosure Rating: 

IP68.

Switch Type: 

CFS2-DXXXX-XX: SPDT;
CFS2-CXXXX-XX: SPST;
CFS2-OXXXX-XX: SPST.

Electrical Rating: 

CFS2-XXAXX-XX

10 (4) A @ 250 VAC;

CFS2-XXBXX-XX

10 (8)A @ 250 VAC;

CFS2-XXCXX-XX

10 (8)A @ 250 VAC;
10 (6)A @ 400 VAC;

CFS2-XXDXX-XX

1 HP @ 125 VAC 16 FLA;
2 HP @ 250 VAC 12 FLA;

CFS2-XXEXX-XX

0.05 A @ 250 VAC.

Shipping Weight:

Housing: 5.43 oz (154 g);
Cable: 0.77 oz (21.27 g) per foot.

Agency Approvals: 

CFS2-XGDSX-XX: UL and CSA approved, all others CE.

5-5/32

[131.00]

1-41/64

[41.50]

6-15/64

[158.50]

4-9/64

[105.00]

3-3/16

[81.00]

L-CFS2:SSS-1000  12/8/10  8:39 AM  Page 1

Remote Site Products  -  1-888-532-2706  -  www.remotesiteproducts.com

http://www.remotesiteproducts.com/p-14404-Dwyer-Mercoid-CFS2-OGDSN-30-Mechanical-Float-Switch.aspx

Summary of Contents for CFS2 Series

Page 1: ...C Phone 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Fax 219 872 9057 e mail info dwyer inst com SPECIFICATIONS Service Compatible liquids Wetted Materials Housing Polypropylene Cable CFS2 XXPXX XX PVC CFS2 XXNXX XX Neoprene CFS2 XXSXX XX 3x16 AWG SJOW CFS2 XXTXX XX Rubber compound EM7 quality CFS2 XXWXX XX EPDM ethylene propylene Temperature Limits 32 to 122 F 0 t...

Page 2: ...tion can be freely adjusted ELECTRICAL CONNECTIONS The Series CFS2 features a variety of different cable options One of these options includes the selection between SPST and SPDT SPST single pole single throw allows a single operating function with the choice of operation on increasing level NC filling or operation on decreasing level NO emptying depending on the model selection SPDT single pole d...

Page 3: ... CFS2 CGXXX XX CFS2 DNXXX XX Figure 4 Filling NC Function Figure 3 Emptying NO Function Figure 5 Double Function Emptying NO Figure 7 Emptying NO Function Figure 9 Double Function Emptying NO CFS2 CNXXX XX Figure 6 Double Function Filling NC Figure 8 Filling NC Function Figure 10 Double Function Filling NC CFS2 OGESX XX CFS2 CGESX XX 2 x 1 CABLE 3G1 CABLE 4G1 CABLE SJOW 3 x 16 AWG CABLE UL APPROVE...

Page 4: ...y the user will void the warranty and could impair the continued safety of the product If repair is required obtain a Return Goods Authorization RGA number and send the unit freight prepaid to the address below Please include a detailed description of the problem and conditions under which the problem was encountered Dwyer Instruments Inc Attn Repair Department 102 Indiana Hwy 212 Michigan City IN...

Reviews: