Bulletin F-MAFS

The Series MAFS Averaging Flow Sensor 

uses evenly distributed total

and  static  pressure  measuring  points  to  deliver  an  accurate
measurement of flows in a duct. The Air Flow Measuring Probe can be
completely  installed  from  outside  of  the  duct  making  it  very  easy  to
install.  With  its  lightweight  and  durable  construction  in  addition  to  its
ease of installation, this product lends itself to being used in the HVAC
industry.    These  air  flow  measuring  probes  may  be  ordered  to  fit  into
either round or rectangular duct installations.

INSTALLATION

When you unpack the Series MAFS Averaging Flow Sensor ensure that
there is no visible damage from shipping.  Inspect each sensing point on
the probes to ensure that they are not filled with debris from shipping. If
there is obvious shipping damage, the probe must be replaced prior to
use in order to avoid inaccurate measurements. Please contact Dwyer
Instruments, Inc. if it is necessary to replace your air flow measurement
probe.

Location

-  The  sensor  should  be  installed  in  the  flowing  line  with  as

much straight run upstream as possible.  A rule of thumb is to allow 10 -
15  diameters  upstream  and  5  downstream.  The  table  below  lists
recommended up and down piping.

CALCULATING VELOCITY

Air Velocity

= 1096.2 (Cp)       Pv

D

where:

Pv  = Sensed pressure difference (velocity pressure)

in inches of water column 

D   =  Air density in lbs./ft.3 (dry air = .075) 
Cp =  Pitot tube coefficient: See specifications for

K-factor vs. size 

Air Density

= 1.325   X   PB

T

PB =  Barometric pressure in inches of mercury

T

=  Absolute Temperature (Indicated Temperature in °F 

plus 460)

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.  Fax: 219/872-9057

e-mail: info@dwyer-inst.com

SPECIFICATIONS
Service:

Clean air.

Wetted Materials:

Aluminum AA6063.

Accuracy:

0 to 9000 FPM (45.7 m/s); ±2% FS, ±3% FS for 6˝ and 48˝

length models.

K-Factor:

0.81, 0.80 for 6˝ and 48˝ lengths, 4˝ length=0.82.

Max. Temperature:

400°F (204°C); Gasket: -31 to 230°F (-35 to 110°C).

Minimum Design Flow:

400 fpm (2.03 m/sec).

Maximum Design Flow: 

12,000 fpm (60.96 m/sec).

Process Connections: 

1/4˝ barb.

Straight Run Requirements:

5 diameters or longest side dimensions.

Specifications - Installation and Operating Instructions

Series MAFS Averaging Flow Sensor

RECTANGULAR DUCT MODELS
Determining Probe Number and Placement for Rectangular Ducts

1. To determine the number of probes you need please consult the 

chart below.

2. In order to determine where to place your probes, divide the short 

duct dimension by number of probes.

3. Divide the result by two and this will be the distance from the top 

edge of the duct to the first probe location.

4. The next probe will be placed two times the resulting distance from 

step two from the first probe. So, if the first probe was placed 4˝ from 
the top edge of the duct, your next probe would be placed 8” from the

first probe, or 12˝ from the top of the duct.

5. Continue this pattern until you have determined all probe locations. 

Example:

You have a duct with a 24˝ short side, and upon consulting the

chart determined that you needed 3 probes for this size duct.

24 / 3 = 8

8 / 2 = 4

Therefore, the first probe is placed 4˝ from the top of the duct.

The second probe is placed 4˝ + 8˝ = 12˝ from the top of the duct.

The third probe is placed 4˝ + (2 x 8˝) = 20˝ from the top of the duct.

Short Duct Dimension
Number of Probes

<12˝

1

12˝ - 23˝

2

24˝ - 35˝

3

36˝ - 48˝

4

1-35/64

[39.37]

21/64

[8.46]

1

[25.40]

49/64

[19.43]

1-11/32

[34.25]

1-3/64

[26.43]

1-13/64

[30.44]

1/4-20

THREADED

STUD

1/2

[12.70]

APPROX.

33/64

[12.95]

29/64

[11.41]

33/64

[12.95]

1/4

[6.35]

1/4

[6.35]

1-1/2

[38.10]

1-1/2

[38.10]

2

[50.80]

4X Ø7/32

[Ø5.54]

2

[50.80]

L

*L dimension = length of part designated in model.

Reviews: