background image

2.1 WIRING ELECTRICAL BOX (ROUGH IN)

Layout the system in terms of wiring: power, analog output, BACnet, relay output, 

digital inputs, analog inputs and plumbing to connect to the monitored spaces. Run all 

power, earth ground, signal communications and analog output wiring into the RSMC 

junction box. Follow all local electrical codes and refer to the wiring diagrams on this 

page and the back label of the RSMC for proper terminal locations. 

The RSMC includes one digital output which may be wired to a local audible or visual 

alarm or may be wired to a controller to indicate an alarm condition. The RSMC contains 

one analog output that linearly corresponds to the reading of the built-in pressure 

sensor. The RSMC contains 2 built-in analog inputs. The analog inputs are capable of 

accepting 4-20 mA, 0-5 VDC, or 0-10 VDC analog transmissions. The analog inputs 

may be assigned as differential pressure, temperature, relative humidity, or air change 

per hour (ACH). One analog input can also be assigned as a digital input for use as a 

door status indicator. This input setup is performed in the input/output menu.

Power supply minimum requirements: 

EN 55032 CISPR 32

FCC Part 15 Subpart B

2.2 ATTACHING PRESSURE TUBING 

Use 1/8˝ or 3/16˝ (3 mm or 5 mm) ID rubber or vinyl tubing (adapters as necessary) to 

transition from any pre-installed tubing to the barbed pressure fittings on the RSMC. 

For the most stable pressure operation, an room pressure pickup installed in the 

reference pressure area is also recommended. 

For measuring a room maintaining a positive pressure, connect one end of tubing to 

the room pressure pickup in the room and the other end to the “+” barbed connection 

on the back of the RSMC. 

For measuring a room maintaining a negative pressure, connect one end of tubing to 

the room pressure pickup in the room and the other end to the “-” barbed connection 

on the back of the RSMC.

3.0 BASIC OPERATION AND SOFTWARE CONFIGURATION

The RSMC home screen is continuously displayed to the end-user, ensuring the room 

environmental conditions are clearly visible. The screen is designed to display room 

parameters, and enable touchscreen operation when changes in room conditions are 

needed, when additional information is desired, or if alarms need to be acknowledged. 

A few of the key elements of the screen are described and shown below. .

The RSMC provides visual representation where each of the parameters are either 

in normal (green), within the caution stage (yellow), in the alarm state (red) and in 

cleaning mode (blue).

The caution (yellow) stage and alarm (red) state are programmed by the supervisor. 

The caution stage can be selected and adjusted to be within a few points from the 

low and high limit setting. As the monitoring parameter comes closer to the set value 

the display will transition from green to an yellow color to warn the staff. If any of the 

parameter readings go outside of the acceptable setting, it will change to a red color, 

start blinking, and the internal built-in audio will begin beeping.

During the alarm state, a speaker icon will show in the middle at the top of the display if 

enabled. Pressing this icon will silence the audible alarm. Adjacent to the speaker icon 

to the left will be a bell icon representing the interlock, if enabled.

Figure 3

2.0 MOUNTING 

The  Series  RSMC  is  designed  to  be  mounted  flush  into  a  wall  or  panel.  Use  the 

included cardboard cut-out as a template to ensure proper wall cut-out dimensions. 

After cutting a 4.21˝ x 7.91˝ hole (107 mm x 201 mm), push the junction box into the 

wall orienting the 2 screw tabs upward and push the box into the cutout, as shown in 

Figure 1. Next use a screwdriver to secure the 2 screw tab wall locks. After the junction 

box is installed firmly into the wall or panel, carefully push the RSMC into the junction 

box as shown in Figure 2 below (after wiring the terminal block). The rear housing will 

snap into the junction box. 

The front panel can be removed from the junction box by pushing downwards on the 

top lip of the bezel. The downward force will release the snap clips, then the front panel 

can be pulled out as shown in Figure 3 below. 

Figure 1

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

POWER

RELA

Y/DIG.

DIG.

RS48

5

AN. OUTPUT

CURRENT

VO

LT

AG

E

-

+

NO

COMMO

N

NC

DIG. INPU

T

DIG. COMMO

N

B+

A-

TERM. RESIST

.

RS485 GN

D

OUTPUT

 +

OUTPUT

 GN

D

UI1 4-20 mA

UI2 4-20 mA

INPU

GN

D

UI1 0-10 

V

UI2 0-10 

V

INPU

GN

D

OUTPUT

FACTORY/PASSWORD

RESET BUTTON

INPU

T

INPUTS

INPUTS

OK

Figure 2

Summary of Contents for StabiliSENSE RSMC Series

Page 1: ...ironment such as a clean room or isolation room and an area outside the room Maintaining a constant differential pressure between the two spaces is critical in ensuring the room is protected by ingress for the outer room or vice versa The RSMC can be programmed to monitor either positive or negative room static pressure in 1 to 3 locations In total it can monitor up to 4 parameters built in differ...

Page 2: ...touchscreen operation when changes in room conditions are needed when additional information is desired or if alarms need to be acknowledged A few of the key elements of the screen are described and shown below The RSMC provides visual representation where each of the parameters are either in normal green within the caution stage yellow in the alarm state red and in cleaning mode blue The caution ...

Page 3: ... and 2 analog or BACnet inputs to be select by the user 2 2 Rooms Monitoring 4 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 2 binary contacts 3 3 Rooms Monitoring 6 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 3 binary contacts wired in series Examples of 1 room 2 room and 3 room setups are ...

Page 4: ...ter For example 0 VDC corresponds to the minimum range of the sensor and 5 VDC corresponds to the maximum range of the sensor In the Measurement box the user can define the type of measurement temperature humidity etc and the desired engineering units to be displayed If ACH Air Changes per Hour is selected duct dimensions need to be entered when the input type is selected as volumetric flow When u...

Page 5: ...try and personnel access Return to Normal delay is the opposite when a parameter value goes out of alarm and now falls within normal range the audible visual and output alarm conditions will persist for this period of time or until the alarm condition is cleared Alarm Deadband is a value that is added or subtracted to a limit when determining if a parameter has returned to a normal state For examp...

Page 6: ...the sensor assigned to the display position to the right next to Select Sensor If the BACnet option is selected the user has to input the BACnet address and sensor type of the remote sensor After completing the room settings the user can select each parameter from each room in order to use it at the alarm configuration or output configuration Each parameter is named with the room name and the sele...

Page 7: ... the output value and the user can also change the state 6 0 MAINTENANCE The Maintenance menu provides several functions that help ensure the RSMC is configured and operating accurately with proper parameters To access the Maintenance menu from the home screen press the Settings icon in the top right corner and select the Maintenance button Within the maintenance menu the following maintenance fun...

Page 8: ...rom the home screen press the Settings icon in the top right corner From the Maintenance menu select Reset A factory reset may help establish a baseline of original functionality from which to build the specific configuration for a given application New configurations can then be added by either touchscreen entry Copy from USB or over the BACnet network Selecting NO will cause the RSMC unit to rem...

Reviews: