10
2.2 Wiring
(Cont’d)
Connectors D and E are input terminals, each requiring p/n SC-CBLE25MM cable / terminal
block assembly.
Thermocouples can be connected to any input of either connector D or E.
For linear inputs (4 – 20 mA or 0 – 5 VDC) it is recommended to connect the wires to the
appropriate terminals for connector D. However, either connector D or E may be used. See
previous page for information on DIP switch settings for 4 – 20 mA inputs.
Any RTD inputs require the RTD module p/n SC-RTD, which includes the cable assembly. In
this case ,p/n SC-CBLE25MM will not be required. Note that (1) SC-RTD will handle up to 12
RTD inputs and can be connected to either connector D (Ch # 1 – 12) or connector E (Ch #
13 – 24).
Instructions for SC-RTD module configuration are in Appendix E.
Connector D (DB-25F)
This Connector provides the Analog Inputs for Channels 1 – 12.
Pinout:
Pin#
Pin
Name
Pin#
Pin
Name
1
Channel 1 (+)
14
Channel 1 (-)
2
Channel 2 (+)
15
Channel 2 (-)
3
Channel 3 (+)
16
Channel 3 (-)
4
Channel 4 (+)
17
Channel 4 (-)
5
Channel 5 (+)
18
Channel 5 (-)
6
Channel 6 (+)
19
Channel 6 (-)
7
Channel 7 (+)
20
Channel 7 (-)
8
Channel 8 (+)
21
Channel 8 (-)
9
Channel 9 (+)
22
Channel 9 (-)
10
Channel 10 (+)
23
Channel 10 (-)
11
Channel 11 (+)
24
Channel 11 (-)
12
Channel 12 (+)
25
Channel 12 (-)