69
APPENDIX E
Instructions for SC-RTD configuration:
The SC-RTD module is required for any inputs to be configured for RTD type
inputs. Each module will accept up to (12) RTD inputs. One would be required for
channels 1 – 12 and another required for channels 13 – 24.
There are total of (4) jumpers for each input on the SC-RTD module. The jumpers
are used to configure each channel input as either “enabled” for RTD inputs or
“disabled” for thermocouple or linear type inputs. The normal configuration is for all
jumpers to be in the enabled position; this would be the default configuration or
status as shipped from Dynalco. If any inputs are determined to be either
thermocouple or linear type (4-20 mA or 0-5 VDC) the corresponding inputs will
need to be disabled by changing the jumper configuration. The jumpers are located
on the PC board which is accessible by removing the cover of the SC-RTD module.
Please call Dynalco for assistance in locating the jumpers and instructions for
configuration.