background image

 

11

6) System 

 
Using the arrows on the keypad, select the “System” icon. 
 
There are (3) display layouts available. Selecting layout A, B or C will define the 
preferred display type as follows: 
 

Layout A:

  Displays groups of (2) input channels plus differential. 

Layout B:

  Displays all inputs as bar graph plus each individual channel. 

Layout C:

  Displays each individual channel in large format. 

 

Note that you are selecting the default layout type. You will be able to change the layout 
during normal operation by pressing the left / right arrows. 

 
 
 
 

Operation

 

 
Once programmed, the UM-600 will begin scanning all enabled channel inputs and will 
initiate alarms based on over / under threshold values configured for each channel. It is 
not necessary to define alarm threshold values for all channels as some may be for 
monitoring only.  
 
 

Alarm Outputs 
 

The UM-600 will alarm when channel values or differential values are above or below 
limits as specified. Alarms can be configured as either latching or non-latching. If an 
alarm condition is met, the red LED on the front panel will blink and the digital output(s) 
will trip. The alarm point name (ch1, ch2, df1, df2) that caused the alarm will be stored 
in memory with date/time stamp info. Non-latching alarms will reset the alarm if its value 
returns to normal. Latching alarms require manual resetting via the front keypad.

 

 
Selecting  the  alarm 

icon will allow you to view any active alarms as well as the 

history log for each channel. Once an active alarm is acknowledged, it will be placed 
into the history log. The history log will continuously store the last 10 alarms for each 
channel as well as the time & date of each alarm occurrence. 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for UM-600

Page 1: ...nel Monitor Installation and Operation Manual Rev B P N145F 12990 PCO 00007462 c Copyright 2010 Dynalco Controls All Rights Reserved Published June 8 2011 MOD TRONIC Instruments Brampton ON 905 457 6322 or 1 800 794 5883 sales mod tronic com www mod tronic com ...

Page 2: ... Types J or K type thermocouple ungrounded 4 20 mA 0 1 VDC 0 5 VDC 0 10 VDC Digital Input Closure to ground indicates run condition or use pulsed input Pulsed Input Magnetic pickup input for RPM display to indicate run condition Alarm Outputs 2 Digital Outputs rated 0 15 A 48 VDC Input Power 10 36 VDC Display Backlit Graphic Display Data Logging Internal Flash Memory to retain alarm history data l...

Page 3: ...om engineering units of measure The keypad implements a menu system which is navigated using the up down left right enter and escape buttons The backlight will turn off after ten minutes of inactivity and will turn on when any of the keys are pressed Installation The UM 600 monitor is a standard DIN package designed to be panel mounted The cutout dimensions are shown below ...

Page 4: ...3 The UM 600 has integral mounting clips for securing into the panel The following drawings illustrate the mounting procedure ...

Page 5: ... PIN Description 1 Power Ground 13 Channel 1 2 Power In 14 Channel 1 3 Ground 15 Channel 2 4 RPM 16 Channel 2 5 Receive Data 17 Channel 3 6 Receive Data 18 Channel 3 7 Transmit Data 19 Channel 4 8 Transmit Data 20 Channel 4 9 Alarm 1 21 Channel 5 10 Alarm 1 22 Channel 5 11 Alarm 2 23 Channel 6 12 Alarm 2 24 Channel 6 ...

Page 6: ...5 Outline Dimensions ...

Page 7: ...ack one screen Advances to next screen Configuration consists of the following steps 1 Setting current date time 2 Enabling each input 3 Defining each input type 4 Defining min max display values for any current or voltage inputs 5 Defining measurement display units PSI mV F C H20 etc 6 Setting over under setpoint trips 7 Selecting either output 1 or output 2 or both for alarm trips 8 Setting eith...

Page 8: ... each input first go to the main programming screen by pressing the Menu Escape key The main configuration screen appears as The various icons are described as Run Signal defines run status input type if any Channel enables each channel type and alarm thresholds Calibration defines zero span values for DCV mA inputs Alarm Logs allows the user to view alarm status Communication Modbus setup System ...

Page 9: ... to be at normal levels If no delay is required set to 0 seconds If Digital is selected you will only need to set the startup delay if applicable Pressing at any time during configuration will prompt you to save the changes Select Yes to save any changes made Selecting No will not save changes 2 Configuration of each Channel Using the arrows on the keypad select the Channel icon Next select the ch...

Page 10: ...resenting a pressure input of 0 500 PSI The Cal Zero and Cal Span values would be defined as Cal Zero 0 Cal Span 500 Note that the Engineering Units would be input as PSI in Channel configuration above Example 2 An oxygen sensor is connected to channel 4 The output of the oxygen sensor is 0 1 VDC 0 1000 mV The Cal Zero and Cal Span values would be defined as Cal Zero 0 Cal Span 1000 Note that the ...

Page 11: ...mplement representation for the signed integers Address Description Data type 30000 Status Register Bits 0 9 Alarms Bit 15 Run Status Unsigned 16 bit integer 30001 30006 Absolute Values for Channels 1 6 Signed 16 bit integer 30007 30009 Differential Values for channels 1 2 3 4 5 6 Signed 16 bit integer 30010 30015 High Alarm Setting for Channels 1 6 Signed 16 bit integer 30016 30018 High Alarm Set...

Page 12: ...efine alarm threshold values for all channels as some may be for monitoring only Alarm Outputs The UM 600 will alarm when channel values or differential values are above or below limits as specified Alarms can be configured as either latching or non latching If an alarm condition is met the red LED on the front panel will blink and the digital output s will trip The alarm point name ch1 ch2 df1 df...

Page 13: ...12 ...

Reviews: