CAUTION:
For single-phase operation, a power supply
cord with suitable cross section defined for single-
phase operation must be used.
CAUTION:
Bridging bar must not be used in 3-phase operation.
CAUTION:
Malfunctions caused by power supply grid are not associated with the
device and are not covered by warranty.
Figure
16.
Bridging bar
ARCEUS 9
CH-
ST
Single-phase
3x10
39
B40-1P
Three-phase
5x2.5
13
B15-3P
ARCEUS 12
MT
-CH-
ST
Single-phase
3x10
52
B63-1P
Three-phase
5x4
17
B20-3P
ARCEUS 15
MT-CH-ST
Three-phase
5x6
22
B25-3P
ARCEUS 18
MT-CH-ST
Three-phase
5x6
26
B32-3P
ARCEUS 24
MT-CH-ST
Three-phase
5x6
35
B40-3P
ARCEUS 27
MT-CH-ST
Three-phase
5x10
39
B40-3P
Device
Power Supply Supply Cord
(mm
2
)
Nominal
Current (A)
Supply Line Minimum
Circuit Breaker Capacity
ARCEUS 6
CH-
ST
Single-phase
3x6
26
B32-1P
Three-phase
5x2.5
9
B10-3P
Table 2. Power Supply Connection Requirements
20