11- ERROR CODES AND DESCRIPTIONS

ERROR TYPE 

DESCRIPTION 

ERROR CODE 

Limit Thermostat 

Protection Error 

This error is displayed if the temperature read by one of the 

central heating outlets or return temperature sensors is above 

107°C. The error must be reset when the temperature reduces to 

85°C. 

H03 

Central Heating Return 

Temperature Sensor 

Error 

This error is displayed if the central heating return temperature 

sensor is short or open circuit, or damaged. Domestic water and 

central heating demands are stopped. When this error is cleared, 

normal operation begins. 

L33 

Central Heating Outlet 

Temperature Sensor 

Error 

This error is displayed if the central heating outlet temperature 

sensor is short or open circuit, or damaged. Domestic water and 

central heating demands are stopped. When this error is cleared, 

normal operation begins. 

L35 

Central Heating Outlet-

Return Sensor Change 

Test Error 

This error is displayed when the central heating outlet temperature 

sensor and return temperature sensor change test fails. The error 

is cleared by reset. 

H80 

Too Frequent Error Reset 

Error 

This error is displayed when 5 error resets are performed within 1 

hour. Domestic water and central heating demands are stopped. 

This error can only be cleared by disconnecting the power to the 

mainboard. 

L13 

10.4- Error Preventive Functions

10.4.1-  Anti  Freeze  Protection:

  During  the  winter  season,  when  the  water  temperature  of  the 

installation  drops  below  6⁰C,  anti  freze  protection  is  activated  and  the  device  keeps  on  heating  until 

water temperature reaches to 15⁰C. Below conditions must be provided and controlled by the customer 

for anti freze protection to work properly:

- Power supply of the device must bu connected

- Radiator valves must be open

- Water pressure of the system should be proper

- Anti freze protection function does not protect your installation, it protects the device

- If the device will not be operated in locations where there is a risk of freezing,  the water of the device

 

should be drained and antifreeze solutions should be used.

10.4.2-  Pump  Anti-Blocking  Function:

  In  situations  that  the  pump  is  not  turned  on  for  24  hours

 

straight, pump is turned on for 5 seconds to prevent it to be stuck. This function is active in error status

 

and stand by mode.

10.4.3- 3 Way Valve Anti-Blocking Function:

 In situations that the 3 way valve is not turned on for 24

 

hours straight, 3 way valve is turned on and changes position for 10 seconds to prevent it to be stuck. If

 

a heat demand occurs during this procedure, anti blocking function is interrupted and the valves takes

 

the position of normal working condtion. This function is active in error status and stand by mode.

 

10.4.

4

- Maintenance Reminder Function:

 After the time period that the device stays connected to the

 

power upply reaches 8760 hours (1 year), the customer is informed that the annual maintenance time

 

has come by flashing “ASE” characters and steady alarm icon on the screen. During this notification,

 

the functionality of the device does not change. If the customer confirms this notification by pressing K1

 

button, timer is reset and the reminder does not appear for another 8760 hours.

In case the customer has periodic maintenance service, service resets the clock and 8760 hour period

 

starts over.

27

Summary of Contents for ARCEUS 12 CH

Page 1: ...ARCEUS ELECTRIC COMBI BOILER ARCEUS 6 9 12 15 18 24 27 kW MT CH ST USER AND INSTALLATION MANUAL...

Page 2: ......

Page 3: ...rams 8 5 4 Detailed View Component List and Installation 12 6 PACKAGING 15 7 ASSEMBLY 15 7 1 Selection of Device s Assembly Location 15 7 2 Wall Mounting of the Device 16 8 CONNECTIONS 17 8 1 Water Pi...

Page 4: ...se from material and workmanship provided that the instructions and warnings in the installation and operation manual are followed The commissioning operation must be carried out by the E C A authoriz...

Page 5: ...on and within the operating pressure range of installation so that freeze protection would be activated The freeze protection remains active even if the device is in OFF closed position 4 4 Commission...

Page 6: ...t breaker Anti freeze Protection for both Central Heating and Domestic Water Circuit Domestic Water Flow Control Pump Jamming Safety 3 Way Valve Jamming Safety Automatic Air Purge Expansion Tank 8 lit...

Page 7: ...US 12 15 18 24 27 MT ARCEUS Monothermic Electric Combi Boiler ARCEUS 6 9 12 15 18 24 27 CH ARCEUS Central Heating Electric Combi Boiler ARCEUS 6 9 12 15 18 24 27 ST ARCEUS Central Boiler Aided Electri...

Page 8: ...at CH Flow NTC CH Return NTC Boiler Tank NTC DHW Solar STB Water Pressure Sensor DHW Outlet Sensor Modbus Communication Cascade Board Wi Fi Board Connection Modulating Room Thermostat Programmable Tim...

Page 9: ...w NTC CH Return NTC Boiler Tank NTC DHW Solar STB Water Pressure Sensor DHW Outlet Sensor Modbus Communication Cascade Board Wi Fi Board Connection Modulating Room Thermostat Programmable Timer Outdoo...

Page 10: ...NTC CH Return NTC Boiler Tank NTC DHW Solar STB Water Pressure Sensor DHW Outlet Sensor Modbus Communication Cascade Board Wi Fi Board Connection Modulating Room Thermostat Programmable Timer Outdoor...

Page 11: ...at CH Flow NTC CH Return NTC Boiler Tank NTC DHW Solar STB Water Pressure Sensor DHW Outlet Sensor Modbus Communication Cascade Board Wi Fi Board Connection Modulating Room Thermostat Programmable Tim...

Page 12: ...ck 4 Neutral Terminal Block 5 Neutral Busbar 6 Cantactor 7 3 Way Valve 8 3 Bar Safety Valve 9 Electric Heaters 10 Main Heat Exchanger 11 Expansion Vessel 12 Drain Valve 13 Plate Heat Exchanger 14 Circ...

Page 13: ...Control Board Figure 6 Control Panel Elements Figure 6 1 Control Board Rear Cover and Terminal Connections 13...

Page 14: ...4 1 MT Model Installation Figurel 7 Monothermic Device Installation Scheme 5 4 2 CH Model Installation Figure 8 CH Device Installation Scheme DHW Outlet DHW Inlet CH Flow CH Flow CH Return CH Return 1...

Page 15: ...dimensions of 735 x 345 x 490 HxWxD as supported by lower and upper styrofoams Boiler Exit CH Exit CH Return Boiler Return 7 1 Selection of Device s Assembly Location The location where the device can...

Page 16: ...as bathtubs shower cabinets and must be assembled at least 50 cm away from these areas Since the outer surface temperature of the device does not exceed 85 C at maximum heating power no special protec...

Page 17: ...3 4 outlet line hot b Domestic water pipe 1 2 outlet line hot c Domestic water pipe 1 2 inlet line cold d Central heating pipe 3 4 return line cold A suitable sized valve should be installed in the w...

Page 18: ...e hot b Boiler outlet line 1 2 hot c Boiler return line 1 2 cold d Installation Filling line 1 2 e Central heating pipe 3 4 return line cold a b c d e Figure 14 ST boiler water connections 8 1 2 HCH M...

Page 19: ...e device for overcurrent protection In case the circuit breaker trips call an authorized service 8 2 Electrical Connection Your combi boiler must be connected to a grounded power line that can supply...

Page 20: ...9 CH ST Single phase 3x10 39 B40 1P Three phase 5x2 5 13 B15 3P ARCEUS 12 MT CH ST Single phase 3x10 52 B63 1P Three phase 5x4 17 B20 3P ARCEUS 15 MT CH ST Three phase 5x6 22 B25 3P ARCEUS 18 MT CH S...

Page 21: ...hermostat T6360 7006907804 E C A Smart Combi Boiler Kit 7006907531 E C A Digital Room Thermostat Cordless Programmable CM727 7006902046 Poly 100 W Room Thermostat 7006903001 E C A Digital Room Thermos...

Page 22: ...er comes out This is done for all radiators The pressure is rechecked via the LCD screen The filling valve is opened and the pressure is allowed to reach 1 5 2 bar Whether there is air in the central...

Page 23: ...ith the central heating circuit temperature increase button the temperature of the heating water in the central heating circuit can be increased to 80 C Domestic Water Temperature Decrease Button With...

Page 24: ...ssword value at parameter menu entry Reduces parameter value Indicates information value Indicates error history value Figure 18 Control Panel Button Configuration 10 2 1 Button Functions K5 K6 K1 K3...

Page 25: ...andby Mode Off Mode It is the mode in which the device can be set to standby mode In this mode central heating and domestic water heating demands cannot be met 10 3 2 Summer Mode In this mode the devi...

Page 26: ...is mode is activated are listed below When the device is powered for the first time or after the power goes out and comes back After a reset process following the overheating error After a high water...

Page 27: ...ture reaches to 15 C Below conditions must be provided and controlled by the customer for anti freze protection to work properly Power supply of the device must bu connected Radiator valves must be op...

Page 28: ...d by pressing the RESET button L43 Water Pressure Sensor Error This error is displayed if the pressure sensor is short or open circuit or damaged When this error is cleared normal operation begins L47...

Page 29: ...hibitor Sentinel X400 etc should be added to the installation water 12 3 Cleaning of Combi Boiler Keep the outer casing of the combi boiler clean by wiping it with a soft damp cloth Do not use strong...

Page 30: ...1 3x10 1 3x10 Power Cord CrossSec on mm 5x6 5x6 5x6 5x10 3 5x2 5 3 5x2 5 3 5x4 Protec on Class IPX4D IPX4D IPX4D IPX4D IPX4D IPX4D IPX4D Sound Level dB 42 42 38 38 38 38 38 Net Weight kg 26 26 27 27 2...

Page 31: ...odel identifier Space Heating Temperature application Medium Efficiency Class Water Heating Load Profile Rated heat output Prated ARCEUS Combi ERP Units CH ST Model Supplier s name or trademark E C A...

Page 32: ...8 U O U n n n n n n nmn n n 9 8 1 6 2 00 1 4 0 3 1 6 5 0 2 9 8 6 6 7 00 2 1 0 3 2 6 2 0 1 4 8aYU8Rna 8 nJ 8cLUFn U Fln E M U ln MUn n n 0 n Bnc8Wn 9cLUFnMan8 Yi n nga n n 81U U8 U BU U U U E U UP F 4...

Page 33: ...33...

Page 34: ...vl8 rvl X7 7 Lv Xh X EZ4T e i 4lz rlh7 l Y 4 h vR I4Y h5 lh4 Xh _ 7 Xh Xd7XhR VY J4Y h4 Y h4 7 0 Q H4 mv 4T T l Xh T 7Y X Xlh e h9 T 7Xe h Ylk hS kFc 4T v 4 vX X4 T lB W v T hS qvR J4X h4 lB T 4lf1 h...

Page 35: ...erial Number Submit Date and Location Maximum Repair Time 20 Work Days Warranty Time 3 Years AUTHORIZED SERVICE Title Address Tel Fax Assembly Date Date Signature and Seal FREE INITIAL START UP COUPON...

Page 36: ...PRODUCTION Organize Sanayi Bolgesi 3 Kisim Mustafa Kemal Boulevard No 13 45030 MANISA Tel 90 236 213 00 21 Fax 90 236 213 08 59 email emas emas com tr www emas com tr 7006910085 2 0...

Reviews: