button no. 1 (position selector) pressed for 3 seconds continuously. When -OFF- is displayed on screen, mode is
activated.
11.3.2- Air Discharge Mode (AP Mode):
It is the process that the device automatically activates to
discharge air in the central heating installation for 160 seconds. In this mode, "AP" is displayed on the screen.
The circulation pump runs for 15 seconds an then stops every 5 seconds in intervals of every 20 seconds. The
three-way valve motor also changes position between a CH-DHW in 40 seconds. The situations where this mode
is activated is listed here below.
•
Once the device is powered for the first time or after the electricity has been switched off and on,
•
After the reset operation following the overheating fault (E03),
•
After elimination of high water pressure (F40) or low water pressure (F37) error,
Do not press 'RESET' while AP mode is active.
11.3.3- Winter mode-Radiator Heating:
If the device in the standby position is set to the winter position,
the appliance will heat the water in the heating circuit until the domestic water is needed. In the winter mode, both
the tap and the radiator icon are displayed on the LCD screen.
When a request for heating is made for radiator, radiator icon flashes (once/second), tap icon stays fixed. When
a request for domestic water is made, tap icon flashes (once/second), radiator icon stays fixed. In this mode,
radiator heating circuit's temperature can be set between 30-80
ͦ
C. For under floor heating applications, the
temperature range can be set between 30-45
ͦ
C.
11.3.4- Summer Mode:
If the device in the OFF position is set to the summer position, the device will only
respond to the domestic hot water demands. In summer mode, the tap symbol appears fixed on the LCD screen,
the radiator icon does not appear. When the domestic hot water is heating request, the tap symbol flashes (1 time
/ second). In this mode, the domestic hot water temperature can be adjusted between 30-65 °C.
11.3.5- Comfort Mod
e
:
The standard operating mode of the device is Comfort mode. By pressing the
"Reset"
button, Eco-Comfort modes can be switched. When Comfort mode is active, "Comfort" icon is
displayed on the LCD screen. Comfort mode is only for radiator heating circuit. It has no effect on use of
domestic water circuit. In this mode, the device responds to fast heating demands by running in modulation.
11.3.6- ECO Mod
e
:
By pressing the "Reset" button, Eco-Comfort modes can be switched. When Eco mode
is
active, "Eco" icon is displayed on the LCD screen. Eco mode is only for radiator heating circuit. It has no effect
on use of domestic water circuit. This mode allows savings on fuel by performing on-off operation.
11.3.7- Maintenance Reminder Mod
e
:
It is the mode where a reminder
for
yearly maintenance is activated. When this mode is active, only "ASE" is
displayed on screen and device continues to meet heating requests. When you see
"ASE" on screen, please get
in contact with E.C.A authorized services for yearly
maintenance.
11.3.8- Anti-Frost Mode:
During the winter season, when the installation
water
temperature falls below
6 ° C, the anti-freeze function is activated and the device continues to operate until the water output of
installation rises to 15 ° C. In order for anti-freeze function to be activated, the following conditions must be
checked and ensured by the customer.
• The power supply of the device must be switched on.
• The gas valve and radiator valves must be open.
• Water pressure of system should be at appropriate level.
• The anti-freeze function helps protect your device, it does not protect your installation.
26
Summary of Contents for Proteus Premix Series
Page 9: ...5 4 Technical Specifications 9 ...
Page 10: ...10 ...
Page 28: ...28 ...
Page 29: ...Table 4 29 ...
Page 32: ...16 INSTALLATION TEMPLATE 16 1 HM Model 32 ...
Page 33: ...E E L C 160 mm 00 160 mm cJiD E E o o L C E 16 2 HCH Model 33 ...
Page 34: ...E E L C 160 mm 00 C 160 mm E E o o L C E 16 2 HST Model 34 ...
Page 36: ...36 ...
Page 37: ...37 ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 41: ...41 ...