CONNECTIONS
Condensate Connection
• All condensing boilers generate condensing discharge. The amount
of the condensate water depends on the working conditions of your
appliance. This can be up to 1.7 litres condensate water an hour.
- The plastic pipe should be fixed to the outlet pipe of the siphon and the pipe should be connected
to drain line.
1)
If national and local requirements do not allow this such a connection, the outlet pipe
of the siphon should be open to connection and should not be closed/blocked.
- If the pipe work is not terminated within the building, the pipe must be insulated against freezing.
- The connection pipes and fittings must be made of plastic material only.
- All horizontal parts must be connected at a slight 2° or 3° downwards incline to ensure to a good
flow.