4
LED INDICATION
Factory Setup:
The display shows the two parameters selected for output 1 and output 2 (according to ordering
code). For digital output versions the display shows RH and T.
User Setup:
The user can change the display layout to 1, 2 or 3 lines and select the
parameters to be displayed by using EE-PCS Product Configuration Software (free download from
www.epluse.com/configurator) and the optional USB configuration adapter (not included in the
scope of supply).
Important:
The EE210-M1xA6 (4...20 mA, 2-wire version) with display operates correctly only if
both outputs are connected.
DISPLAY
SELECTION OUTPUT SIGNAL U/I
The factory setup of the output signal and scaling corresponds to the type number as ordered.
The output signal (voltage or current 3-wire) can be selected with the DIP switch on the main electronics board (see picture PCB
EE210-M1xA2/3/5). This does not impact on the scaling of the outputs, which can be changed using USB configuration adapter and
the EE-PCS.
Examples
Factory setup: voltage output 0 - 5 V or 0 - 10 V corresponds to 0…100%RH.
After switching from U to I: current output 0…20 mA corresponds to 0…100%RH.
A change of the current output range for instance to 4 - 20 mA (3-wire) can be made subsequently with the USB configuration adapter
and EE-PCS.
Factory setup: current output 0 - 20 mA corresponds to -10…50 °C.
After switching from I to U: voltage output 0 - 10 V corresponds to -10…50 °C.
A change of the voltage output range for instance to 0 - 5 V can be made subsequently with the USB configuration adapter and
EE-PCS.
Green LED
Information during normal operation
Blue LED
Information during setup with the optional USB
configuration adapter HA011066 and the EE-PCS
Product Configuration Software
on
= everything OK
on
= USB stick connected to PC, no communication
with EE-PCS
flashing = the main board does not recognize the
measurement electronics inside the RH probe
flashing = communication in progress with EE-PCS
off
= no power supply or main board failure
off
= USB stick not connected to PC
HARDWARE BUS TERMINATION
If required, the bus termination shall be realized with 120 Ohm resistor, jumper on the board.
• Jumper mounted
= bus terminated
• Jumper not mounted = bus not terminated
ADDRESS SWITCH
Address Switch
Address Switch
Address setting via EE-PCS Product Configuration Software
All DIP switches at position 0 → address has to be set via
Product Configuration Software
Factory setting: 242 (permitted values: 1…247).
Example: Slave address is set via configuration software.
Address setting via DIP switch
Setting the DIP switches to any other address than 0, overrules the
slave address set via configuration software (permitted values: 1…247).
Example: Slave address set to 11 (= 0000 1011 binary).
0 0 0 0 0 0 0 0
0
1
1 1 0 1 0 0 0 0
0
1
DIGITAL SETTINGS