User Manual EE212
Modular Humidity and Temperature Sensor | 15
Address Switch
Address setting via DIP switch
Modbus
(slave device): Setting the DIP switches to any other address than 0,
overrules the Modbus address set via EE-PCS
(permitted values: 1…247).
BACnet
(master device): Setting the DIP switches to any other address than
0, overrules the BACnet address set via configuration software. BACnet Note:
permitted values are 0…127. The 8th bit of the DIP switches is ignored (ID 127
= 0111 111). To set address 0 via DIP switches, the 8th bit shall be set to 1 (ID
0 = 1000 0000).
Example: Address set to 11 (= 0000 1011 binary).
1 1 0 1 0 0 0 0
0
1
5.2.3. BACnet Protocol Settings
Factory settings
User selectable values (via EE-PCS)
Baud rate
As per type number ordered
9 600, 19 200, 38 400, 57 600, 76 800, 115 200
Data bits
8
8
Parity
None
None
Stop bits
1
1
BACnet address
46
0…127
Tab. 2
BACnet protocol settings
PLEASE NOTE
The recommended settings for multiple devices in a BACnet MS/TP network are 38 400, 8, none, 1.
The EE212 PICS (Product Implementation Conformance Statement) is available on the E+E website at
BACnet address and baud rate can be set via:
▪
EE-PCS Product Configuration Software and the USB configuration adapter HA011066.
▪
BACnet protocol, see the PICS.
5.2.4. Modbus RTU Protocol Settings
Factory settings
User selectable values (via EE-PCS)
Baud rate
As per type number ordered
9 600, 19 200, 38 400, 57 600, 76 800, 115 200
Data bits
8
8
Parity
Even
None, odd, even
Stop bits
1
1, 2
Modbus address
46
1...247
Tab. 3
Modbus RTU protocol settings
PLEASE NOTE
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.