3.2.6 Operating components EE245
1. Interval rotary-switch „TIME“
2. Push-button „CONNECT“
4. Battery compartment
3. Jumper „J1“ (EXT/BAT)
6. CO2-Module
5. Humidity-Module
1. Interval rotary-switch “TIME”:
With the rotary switch “TIME”, the following transmission and measurement intervals can be selected:
Switch positon
Interval
0
20 sec.
1
30 sec.
2
45 sec.
3
1 min.
4
2 min.
5 = default
5 min.
6
10 min.
7
15 min.
8
20 min.
9
30 min.
Switch positon
Interval
A
45 min.
B
60 min. (1 hr)
C
90 min. (1,5 hr)
D
120 min. (2 hr)
E
180 min. (3 hr)
F
240 min. (4 hr)
Attention:
With the webserver (EE242 Base Station), any time interval can be configured. Selecting a
time interval of less than 15 minutes for the transmitter will greatly reduce the operating life of the
batteries. Typical operating life is up to 3 years, based on a transmission interval of 15 minutes (for T /
%RH).
2. Push-button „CONNECT“:
To establish the initial connection between the base station and the transmitter.
(For a detailed technical description, see chapter 4. “Starting up the Wireless System”.)
Additionally the status of "signal strength level [%]" can be activated temporary with this key. If you
press the key for 1 sec while connecting the voltage supply (or the last battery is inserted) the EE244
shows the "signal strength level [%] of the wirless connection for 60 sec before switching back to the
normal display mode.
3. Jumper „J1“ (EXT/BAT):
The allocation of the jumper allows for the selection of ‘battery power’ or ‘external power’.
4. Battery compartment:
Alkaline batteries, 4 off (1.5V, AA)
13
Operating manual Series EE240 Wireless sensor