9
User Manual EE600 Differential Pressure Sensor
Fig. 9
Pressure hose route
Important: Make sure to connect the higher pressure at the “+” pressure connector and the lower
pressure at the “-“ pressure connector. Inverted connection leads to “out of range” information on the
optional display and at the analogue outputs, see 5.1.7 Outputs and 3.4.2 Display.
Level indication
h
Fig. 10
Mounting examples
5 Setup and Configuration
The EE600 is ready to use with its factory settings. The user can change the factory setup with the on-
board DIP switches or the PCS10 Product Configuration Software and the USB configuration adapter
(order code HA011066), please refer to the chapters below.
5.1 Analogue Version
Each EE600 is delivered with the following factory settings (all switches on “0“):
Measurement range:
100 % of the full scale (1 000 Pa or 10 000 Pa)
Response time:
50 ms
Displayed unit:
Pa
Display backlight:
on
Output signals:
0 - 10 V and 4 - 20 mA
Source of settings:
DIP switch settings (only available with auto-zero version)
The analogue version is intended to be configured with the on-board DIP switches. With the auto-zero
version, all the changes to the factory setup can also be done with the PCS10.
Settings that can be changed with PCS10:
Application settings (see chapter 5.4.1 Application Settings)
Display visualisation (see chapter 5.3.2 Analogue Version with PCS Settings or Digital Version)
Measurands and their measuring range
Auto-zero on/off and interval (see chapter 6.3.4 Auto-zero (Optional))
Response time