Address Switch

Address Switch

Address setting via EE-PCS Product Configuration Software:

All Dip-Switches at position 0 → address has to be set via Product Configuration Software 

Modbus 

(Slave device): factory setting EE650: 65 (permitted values: 1…247).

BACnet

 (Master device): factory setting EE650: 65 (permitted values: 0…127).

Example: Slave address is set via configuration software.

Address setting via Dip-Switch:

Modbus

 (Slave device): Setting the Dip-Switch to any other address than 0, overrules the slave 

address set via configuration software (permitted values: 1…247).

BACnet 

(Master device): Setting the Dip-Switch to any other address than 0, overrules the slave 

address set via configuration software.

BACnet Note:

 permitted values are 0…127. The 8th bit of the Dip-Switch is ignored 

 

(ID 127 = 0111 111).

To set address 0 via Dip-Switch, the 8th bit shall be set to 1 (ID 0 = 1000 0000).

Example: Slave address set to 11 (= 0000 1011 binary).

FLOAT (read register):

Function code /  

Register number

1)

 [Dec]

Register address

2)  

[HEX]

Parameter 

name

31003

0x03EA

Temperature 

[°C]

31005

0x03EC

Temperature 

[°F]

31041

0x0410

Airflow 

[m/s]

31043

0x0412

Airflow 

[ft/min]

SHORT (read register)

3)

:

Function code /  

Register number

1)

 [Dec]

Register address

2)  

[HEX]

Parameter 

name

34002

0x0FA1

Temperature*  

[°C]

34003

0x0FA2

Temperature** 

[°F]

34021

0x0FB4

Airflow*  

[m/s]

34022

0x0FB5

Airflow*** 

[ft/min]

* Values are stored with the scale 1:100 (e.g.: 2550 is equivalent to 25.5 °C)

** Values are stored with the scale 1:50 (e.g.: 2550 is equivalent to 51 °F)

*** Values are stored with the scale 1:1

INFO (read register):

Function code /  

Register number

1)

 [Dec]

Register address

2)  

[HEX]

Parameter 

name

30001

0x00

Serial number (as ASCII)

30009

0x08

Firmware version

INTEGER (write register):

Function code /  

Register number

1)

 [Dec]

Register address

2)  

[HEX]

Parameter 

name

60001

0x00

Slave-ID* (modbus address)

60002

0x01

Modbus protocol settings

3)

*  If the ID is set via DIP-Switch the response will be NAK.

Please see PICS (Product Implementation Conformance Statement)  - available on 

www.epluse.com

BACnet Setup

Address Setting

QUICK GUIDE

EE650 - Air Velocity Tra

nsmitters with RS485 Interface

(Full User‘s Guide at www.epluse.com/EE650)

V+

GND

V+

A (=D+)

RS485

B (=D-)

GND

AV

1
2
3

1
2
3
4

+

-

~

~

+

-

~

~

V / mA

Digital interface

power supply

24 V AC/DC ±20 %

Wiring

Hardware

The bus termination shall be realized with 120 Ohm resistor, switch on the board.

Very important: 

For proper function the power supply must be strong enough to ensure supply voltage within the specified range (see technical data) 

at any time and at all devices in the bus. This is particularly relevant when using long and thin cables which can cause high voltage 
drop; please note that a single EE650 requires peak current of 150 mA.

0 0 0 0 0 0 0 0

0
1

1 1 0 1 0 0 0 0

0
1

Modbus Setup

1) Register number starts from 1

2) Register address starts from 0

3) For Modbus protocol setting please see  Application Note Modbus (www.epluse.com)

S1 S2

ON

S1

:  Response time t

90

 

ON: slow

 

OFF: fast

S2

:  Termination resistor 

 

 

120 Ohm

 

ON/OFF