Address Switch
Address Switch
Address setting via EE-PCS Product Configuration Software:
All Dip-Switches at position 0 → address has to be set via Product Configuration Software
Modbus
(Slave device): factory setting EE650: 65 (permitted values: 1…247).
BACnet
(Master device): factory setting EE650: 65 (permitted values: 0…127).
Example: Slave address is set via configuration software.
Address setting via Dip-Switch:
Modbus
(Slave device): Setting the Dip-Switch to any other address than 0, overrules the slave
address set via configuration software (permitted values: 1…247).
BACnet
(Master device): Setting the Dip-Switch to any other address than 0, overrules the slave
address set via configuration software.
BACnet Note:
permitted values are 0…127. The 8th bit of the Dip-Switch is ignored
(ID 127 = 0111 111).
To set address 0 via Dip-Switch, the 8th bit shall be set to 1 (ID 0 = 1000 0000).
Example: Slave address set to 11 (= 0000 1011 binary).
FLOAT (read register):
Function code /
Register number
1)
[Dec]
Register address
2)
[HEX]
Parameter
name
31003
0x03EA
Temperature
[°C]
31005
0x03EC
Temperature
[°F]
31041
0x0410
Airflow
[m/s]
31043
0x0412
Airflow
[ft/min]
SHORT (read register)
3)
:
Function code /
Register number
1)
[Dec]
Register address
2)
[HEX]
Parameter
name
34002
0x0FA1
Temperature*
[°C]
34003
0x0FA2
Temperature**
[°F]
34021
0x0FB4
Airflow*
[m/s]
34022
0x0FB5
Airflow***
[ft/min]
* Values are stored with the scale 1:100 (e.g.: 2550 is equivalent to 25.5 °C)
** Values are stored with the scale 1:50 (e.g.: 2550 is equivalent to 51 °F)
*** Values are stored with the scale 1:1
INFO (read register):
Function code /
Register number
1)
[Dec]
Register address
2)
[HEX]
Parameter
name
30001
0x00
Serial number (as ASCII)
30009
0x08
Firmware version
INTEGER (write register):
Function code /
Register number
1)
[Dec]
Register address
2)
[HEX]
Parameter
name
60001
0x00
Slave-ID* (modbus address)
60002
0x01
Modbus protocol settings
3)
* If the ID is set via DIP-Switch the response will be NAK.
Please see PICS (Product Implementation Conformance Statement) - available on
www.epluse.com
BACnet Setup
Address Setting
QUICK GUIDE
EE650 - Air Velocity Tra
nsmitters with RS485 Interface
(Full User‘s Guide at www.epluse.com/EE650)
V+
GND
V+
A (=D+)
RS485
B (=D-)
GND
AV
1
2
3
1
2
3
4
+
-
~
~
+
-
~
~
V / mA
Digital interface
power supply
24 V AC/DC ±20 %
Wiring
Hardware
The bus termination shall be realized with 120 Ohm resistor, switch on the board.
Very important:
For proper function the power supply must be strong enough to ensure supply voltage within the specified range (see technical data)
at any time and at all devices in the bus. This is particularly relevant when using long and thin cables which can cause high voltage
drop; please note that a single EE650 requires peak current of 150 mA.
0 0 0 0 0 0 0 0
0
1
1 1 0 1 0 0 0 0
0
1
Modbus Setup
1) Register number starts from 1
2) Register address starts from 0
3) For Modbus protocol setting please see Application Note Modbus (www.epluse.com)
S1 S2
ON
S1
: Response time t
90
ON: slow
OFF: fast
S2
: Termination resistor
120 Ohm
ON/OFF