User Manual HTS801
Humidity and Temperature Sensor for High Humidity and Chemically Polluted Conditions | 31
Removing the probe
1.
Hold firmly the probe to avoid it being suddenly expulsed when releasing the lock. Do not bend damage the
probe cable.
2.
Loosen slowly the lock nut with a spanner (spanner width 24) only till the probe is pushed out by the
overpressure in the process. Do not completely loosen the lock nut, but only as much as necessary for the
probe to slide.
3.
After the probe has been pushed out of the process up to the stop, close the ball valve.
4.
Remove the probe from the ball valve.
NOTICE
Observe the correct positioning of the sealing element 1 before reinstalling the probe.
4.7
Remote Sensing Probes Type T17
code “cable length”
1)
code “probe length”
1)
∅
12
(0.5)
1/2".ISO.or.1/2".NPT
RH
Optional cut-in fitting
see accessories datasheet
code “cable length”
1)
150 (5.9)
∅
6
(0.24)
1/2".ISO.or.1/2".NPT
T
Optional cut-in fitting
see accessories datasheet
4.7.1.
Installation at Normal Pressure
RH probe
HA010207
T probe
HA010201
Fig. 32 Mounting of sensing probe with flange (accessory)
A.mounting.flange.12.mm.(1/2").for.the.humidity.probe.and.a.mounting.flange.6.mm.(1/4").for.the.temperature.
probe are available as an accessory. The immersion depth is adjustable.
Order codes:
RH probe (12 mm (1/2"))
T probe (6 mm (1/4"))
Flange
HA010201
HA010207