Digital Protector

Voltage – Current
         and 
Frequency control

ke-DP01

Phase Sequence Control

Under Voltage Protection

Unbalanced Voltage  
Protection

Over Frequency 
Protection

Under Frequency 
Protection

TRUE  RMS

Latch Function

V

L1

,

V

L2,

V

L3

V

L12,

V

L23,

V

L13

I

L1,

I

L2,

I

L3

Hz

Gen

n

eral:

In three phase systems, it measures RMS values of AC voltages

,

(Select) phase-neutral voltages and phase-phase voltages monitor 
sequentially.
ke-DP01 has many  features. 
Those are;
- Phase Failure

(seq)

- Phase Sequence 

(seq)

- Over Voltage Protection

(o - U)

- Under Voltage Protection

(u - U)

- Voltage Unbalance (asymmetry) Protection

(u

n

b)

- Over Current Protection

(o - C)

- Under Current Protection

(u - C)

- Current Unbalance (asymmetry) Protection

(ubC)

- Over Frequency  Protection

(o - F)

- Under Frequency  Protection

(u - F)

When device is turn on if its adjusted voltages and frequency in its 
interval and if phase sequence is correct relay  sw itch on.
If any of error occurred ( except phase failure and phase sequence ) 
at the end of adjusted time relay sw itch off its contact. When system
return normal  values, at the end of time out relay sw itch on.

L1

L2

L3

Re

< t-1

t-1

Phase Failure:  (u-U)

Before starting system , it controls phase absence then if all phases  
exits Normal LED turn on and relay  contact  sw itch on. In case of 
missing of any L1,L2,L3 phases , Normal LED turn off  and relay  
sw itch  off its contact .In this case 

u-U 

w arn appears

 

on display.

Special Button

n

s:

V

L2

V

L3

L1

L2

L3

V

L12

L1

L2

L3

V

L23

L1

L2

L3

V

L13

Select: 

(Up direction) 

w hen pressing continuously, 

system. When button release 
device continue to show  voltage. 

Reset: 

If error case although disappeared 
then device is not return to normal

,

 

latch-function occurred and it 
makes locked device. 
Or Lock-function (only for 
currents) may be occured.
After checking error in system 
then  restart device w ith pushing 
reset button.

IM PORTANT:

  L1 - N  is device supply inputs. Thus,the applied L1 – N 

voltage must be rated voltage of  system . Otherw ise normal led 
makes flash and the device sw itched off its output contact.
The measured frequency also  must the  frequency  of the system.

n

n

n

n

,

,

n

,

, ,

,

Phase Sequetion

n

:  (Seq)

In case of w rong phase order , Normal LED turned off and relay 
contact is not sw itch  on. In this case 

seq

  w arn appears on the 

screen. If  phase order is corrected , Normal LED turned on and out 
relay sw itch on.

, ,

, ,

Over Voltage Protection

Under Current Protection

Unbalanced Current  
Protection

Over Current Protection

L1

L2

L3

L1

L2

L3

Display Fun

n

ction

n

s:

AREAS OF OPERATION:

■  In-Elevator motors protection
■  On-pump and electric motor 
■  Resistance in oven w ith

w w w . e k t

2

. c o m

Electronics 

Katrangi

 Trading

Voltage Unbalanced:  (unb)

The phase-phase voltage unbalance limit can be adjusted  betw een
(5% - 20%) . When it exceeds the adjusted limit , the device 
sw itched off its out contact at the end of  t-1 delay. In this case  

unb

 w arn  appears on the screen. For the returning normal state  

case at the end of t3 time Normal LED turned on and output contact 
sw itch on. If the phase-phase voltage  unbalance, return adjusted 
value shorter than  t-1 time  output relay does not release its 

unb

 = 000(oFF) protection is disable .

Exam ple:

 Let's say that asymmetry value is set to %15 for a 

3 x 380VAC. 
In this case  relay contact sw itch off  at (380-(380x0.15))=323 V.
Sw itch on the contact is performed at 323+(380x%15x%20)= 334V. 

Re

L1 L2 L3

L2 L3

L1
L2
L3

hy s

+ % unb

V

nom

hy s

Lev el

Re

- % unb

t-1

< t-1

t-1

L1 L3 L2

L1 L2 L3

r-t

r-t

    (V

max 

- V

min

 % unb  =

            x 100      Hys = 380 x (% Asm) x (% 20)

         380

currents and system frequency sensitively. Using up direction button 

 

p

f

f

screen dis l ys  frequency o  

a

asymmetry values should under  20% (hysteresis value). In this 

contact. Hysteresis is 20 %.

(%20 is the hysteresis).

V

L1

L1

L2

L3

Summary of Contents for ke-DP01

Page 1: ...be occured After checking error in system then restart device w ith pushing reset button IMPORTANT L1 N is device supply inputs Thus the applied L1 N voltage must be rated voltage of system Otherw ise normal led makes flash and the device sw itched off its output contact The measured frequency also must the frequency of the system n n n n n Phase Sequetion n Seq In case of w rong phase order Norma...

Page 2: ...lue exceeds the adjusted value w ithin the start delay time the device sw itches off its output contact immediately Very Over Current value o C x VOC This function can be disable if VOC 000 oFF Over Curren n t Coefficie n t OC Current Sudden Sw itch Off Protection delay time the device sw itches off its output contact immediately Over Current value o C x OC This function can be disable if OC 000 o...

Page 3: ... sec Over Frequency o F u F 0 4 70 Hz oFF function is disabled Under Frequency u F 40 Hz o F 0 4 oFF function is disabled Accessing Voltage Parameter Accessing Curre n t Parameter Current transformer Primer value Ct Ct 000 001 005 000 A 5 1000 A Over Current o C oFF function is disabled H ysteresis Value hYS 00 3 3 0 50 50 Delay Time for Current d t 0 1 60 sec Start Delay Time Sdt 0 1 60 sec oFF f...

Page 4: ...rement Range for seconder current 0 05 6 Amp AC Voltage Measurement Range Phase Phase 10 500 Vac 45 65Hz Phase Neutral 10 300 Vac 45 65Hz For pow er supply L1 N 176V 242V Voltage Measurement Pow er Consumption 1VA for one phase Measurement Sensitivity 1 1 digit Contact Current Max 3A 240Vac Device Protection Class IP 20 Connector Protection Class IP 00 Temperature 5 C 50 C Connection Type To conne...

Reviews: