background image

CLASS 3400 METER

19

62-0391-03

IMPORTANT: 

When looking from the source side of the conductor(s) being monitored, you 

should see the arrow on the current sensor assembly. The arrow should be 

pointing in a clockwise direction around the conductor(s) being monitored. If 

the arrow is not positioned on the source side, inaccurate readings will result.

6.4.2 Current Sensor Wiring

Once the current sensors are installed onto their appropriate phase conductors, you 

can begin terminating the current sensors onto the Class 3400 main board. The 

current sensors can be extended up to 500 feet for remote monitoring applications. To 

extend the length of the wires, use #22 AWG twisted-pair wire with one white and one 

black wire.

The easiest way to connect the current sensors is to use the meter’s built-in current 

sensor diagnostics. To do this, there must be at least 1% of the meter’s current rating 

(amps) flowing in each of the conductors being monitored. The Class 3400 meter’s 

diagnostic program will provide data to ensure that the current sensor installation is 

done properly.

The current sensor connection points are located at the bottom right of the main power 

board. These are terminals 5 through 10 of terminal block TB1. Each sensor connects 

to two terminals one labeled “Black” and the other “White.” Current sensors should be 

connected to the meter one at a time and verified using the current sensor diagnostic 

program.

Connect one of the current sensors to TB1 terminals 5 and 6 (Phase A). Wait 5 

seconds and look at the meter display.

If the meter displays an error message (see below), remove the wires from terminals 5 

and 6 and install them on terminals 7 and 8 (Phase B). if an error message occurs with 

the sensor attached to terminals 7 and 8, try again on terminals 9 and 10 (Phase C). 

The “CT Error:“msage will disappear when the current sensor is connected to the 

correct terminals (phase).

Error Messages: 

CT ERROR: A 

CT ERROR: A B 

CT ERROR: A C 

NOTE: The Single-Phase option will only display errors for A and B. 

Refer to the section on Current Sensor Diagnostics for assistance in troubleshooting 

these errors. 

6.4.3 Main Power

After the meter circuit wiring has been examined for correctness, power may be 

applied to the circuit board. There are three LEDs located in the upper right corner of 

the Meter Board labeled BEAT, STATUS and LOAD. The BEAT and STATUS LEDs will 

blink once per second when the meter is operating normally, twice per second if there 

is a problem.If the monitored circuit is under load the LOAD LED will actively blink. A 

heavy load will cause the LED to blink faster than a light load. Very light loads will 

result in an extended blink time. 

Summary of Contents for Class 3400 Meter

Page 1: ...62 0391 03 INSTALLATION INSTRUCTIONS Class 3400 Meter ADVANCED KWH DEMAND METER WITH COMMUNICATIONS E Mon 1985 Douglas Drive North Golden Valley MN 55422 www emon com info emon com...

Page 2: ...ed with your products we provide toll free technical and sales support Monday through Friday 8 00 am to 7 30 pm EST 800 334 3666 You may also reach us via email at info emon com If you have questions...

Page 3: ...16 Section 6 6 Line Voltage Current Sensor Diagnostics 16 Section 6 7 RS 485 Wiring 18 Section 6 8 RS 232 Communications 19 Section 6 9 Modem Wiring 22 Section 6 10 Modbus RTU Wiring 25 Section 6 11 B...

Page 4: ...proper installation of this meter Verify the input voltage rating and configuration on the unit panel label to ensure that it is suitable for the intended electrical service 3400 meters labeled for 12...

Page 5: ...or The protection and safety features provided by this equipment may become impaired or otherwise compromised NOTE If any trouble arises during installation or functional verification opera tions do n...

Page 6: ...is connected to the correct terminals One three terminal screw connector RS485 is for RS 485 communications One two terminal screw connection output is for a pulse output One RJ 45 jack J8 is provide...

Page 7: ...nd the board mounts on the inside of the housing door No additional connections to the display board are required The display board s LCD readout indicates the metered values as well as errors associa...

Page 8: ...Type kit split core scs solid core non supplied blank Brand Class Voltage Amperage Enclosure Communication Protocol Current Sensor Option Current Sensor Option Current Sensor Option Example E 34 208...

Page 9: ...Pollution Degree Degree 2 In Accordance With IEC 664 Installation Overvoltage Category Category III Measurement Category Category III Enclosure Material UL Type 1 JIC Steel or Type 4X Plastic Rain Tig...

Page 10: ...ed CAT 5e cable 8 conductor stranded 24 AWG Cable Connector RJ 45 termination protocol 10 100 base T Cable Distance 450 feet Load Control Contacts Contact Closure Set by user Contact Rating 28Vdc 10A...

Page 11: ...io or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or re...

Page 12: ...hock exists Prior to performing any wiring operations review all contents of the user manual and de energize the MAINS power switch Only qualified personnel should perform installation wiring Installa...

Page 13: ...s must be installed indoors 6 2 Main Power Board Connections 1 Installing a temporary ground for ESD protection With all circuits de energized connect a temporary protective earth ground con nection f...

Page 14: ...ing of the enclosure 4 Unit MAINS Wiring The first four positions of terminal block TB1 located at the bottom left corner of the main power board are clearly labeled Phase A B C N neutral Earth Ground...

Page 15: ...ach of their respective terminal block positions and tightened down verify that each terminal block screw is securely fas tened by gently tugging on each conductor NOTE On Single phase order SP option...

Page 16: ...Repeat Step F Once the meter displays the correct line voltages and there are no error messages you are ready to connect the current sensors to the meter Before continuing with the installation verify...

Page 17: ...CLASS 3400 METER 17 62 0391 03 NOTE The meter will be reset later via the software during startup proce dures...

Page 18: ...3400 meters are supplied with this sensor type 2 Solid core current sensor This sensor does not open and requires the monitored conductor to be removed from the circuit to install the current sensor T...

Page 19: ...sor connects to two terminals one labeled Black and the other White Current sensors should be connected to the meter one at a time and verified using the current sensor diagnostic program Connect one...

Page 20: ...2 AWG SENSOR CONNECTIONS W WHITE LEAD B BLACK LEAD NEUTRAL NOT USED IN DELTA SYSTEM LITTLEFUSE PART NUMBER KLDR 100 1 10A 600 VAC INLINE FUSE PER CONDUCTOR LITTLEFUSE PART NUMBER KLDR 100 1 1 1 1 LINE...

Reviews: