background image

Chapter 1
Load Control Relay Option Description

The Class 3000 load control relay is designed to operate at user-selected high 
and low set points. This provides the user with the capability to reduce a 
facility’s electrical (kilowatt) demand. By proper selection of the high kW limit, 
the meter can be utilized to shave expensive electrical demand peaks by shed-
ding loads or by activating a local generator. The low kW limit set point will 
allow the load to be re-established or will shut down the local generator.

A user-selectable timer (

ramp

) will delay relay activation to eliminate short-term

“nuisance” functioning, such as short-term motor start loads or compressor 
burdens. Once activated, the relay has a second user-selectable timer (

hold

), 

which keeps the relay active if the load falls below the low set point immediately 
after operation. This is designed to prevent short time cycling such as could 
occur in the control of an HVAC compressor, for example. The factory preset 
for high-limit threshold is 30 seconds (adjustable range is 15-240 seconds); the 
“hold” preset is 60 seconds (adjustable range is 60-2400 seconds).

The form “C” relay is mounted on the main meter board, which is located on 
the back of the enclosure. It is capable of controlling 240VAC @ 3 amps. The 
connection to the relay is through a three-screw terminal block (TB-5) located 
next to the relay. The terminal block is removable to provide easy wiring of the 
normally open or normally closed contacts. The relay option must be ordered 
with the meter, as it is not field-installable.

All relay functions are programmed through four pushbuttons located on the 
meter’s display board, which is mounted on the door of the enclosure.

High and low thresholds are shown on the Class 3000’s display screen during
programming. The display also shows the value of the two built-in timers. 
During normal meter operation, the display provides the high and low 
thresholds while also showing the “real-time” load in kilowatts (demand).

Installation should be performed by qualified personnel and only according to 
all applicable electrical codes. E-Mon and its representatives assume no
responsibility for damage or injury resulting from the improper installation of 
this meter.

3

2

Chapter 2
Load Control Relay Wiring

The Class 3000 load control relay is mounted on the main meter board inside the 
enclosure and is capable of controlling 240VAC @ 3 amps. 

Under no circum-

stances should voltage or current exceed these limits.

 The connection to the 

relay is through a three-screw terminal block (TB-5) located next to the relay. This 
terminal block is removable to make wiring easier.

The relay is for pilot operation and should not be used for direct load control where 
the load is above the 3-amp limit. However, it may be utilized for directly functioning 
an alarm, again with precautions that the alarm load stays below the 3-amp rating.

Wiring

All wiring must be done in accordance with national and local electrical 
codes, and only by qualified personnel.

Remove the three-screw terminal block from the circuit board by pulling it up and 
away from the board. Connect the wires that are being used for the control/alarm 
circuit to the terminal block. The control circuit wires should not be energized until 
the installation is complete. The relay is a form “C” device and can be wired nor-
mally open (NO) or normally closed (NC), depending on desired functionality.

Re-install the terminal block onto the board by inserting it into the TB-5 socket.

Program the meter for the correct set points as described in Chapter 3.

TB-5

TB-5

R

NO

P

NC

....

Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176

FAX 781.665.0780 - TestEquipmentDepot.com 

Reviews: