DIN-MON™ SMART METER
62-0442—05
28
NOTE: If you have connected the current sensor to all terminals and the error
message is still appearing, reverse the black and white wires and repeat
the previous steps until the correct connection is found. If the CT Error
message is eliminated, you have found the correct sensor connection;
however, the current sensor was not installed properly around the con-
ductor, or the sensor wires were extended and not spliced together cor-
rectly.
Correct the sensor installation by reconnecting the black wire to the
black terminal and the white wire to the white terminal on the plug and
reinstall the plug into the correct phase terminal for that current sensor.
The error message should be eliminated and the current sensor is now
installed properly.
If the CT Error message has not been eliminated at any time while trying all 3 inputs
both ways, check the AC voltage output from the current sensor leads between the
black and white wires using an AC voltmeter. If the reading on the AC voltmeter is
close to or at zero, this indicates a very light load on the circuit or that the current
sensors are not secured properly (check connection between current sensor halves or
the lead splices to ensure they are tight).
Once the first current sensor is connected properly and the error message has been
eliminated, repeat the previous procedure for the remaining current sensor(s). When
all error messages have been eliminated and all sensors are installed correctly, the
meter is operational.
When the meter is properly connected, replace Mains / Current Sensor cover and
secure with cover screw.
Wait 5 seconds and check the meter display.