1. Application
2. Technical data
Electronic timer
e.control.t08m
(hereinafter referred to as timer) is used for realization of time functions in the control systems and automati-
on. It operates according to the set time schedule planned by the user.
The timer meets requirements of
EN 60730-1, EN 60730-2-7
.
The product must be operated under the following environmental conditions:
• non-explosive;
• does not contain corrosive gases and vapors in concentrations destroying metals and insulation;
• not rich conductive dust and vapors;
• lack of direct exposure to ultraviolet radiation;
• should not be significant shock or vibration.
Transportation and storage are only permitted in the original packaging.
See Pic. 1.
See Pic. 4.
At the first inclusion or reset, timer can be setting with buttons «
▲▼
» and «OK».
See Pic. 5.
See Pic. 6.
See Pic. 7.
If there is no activity for 1 minute, the timer will automatically exit from the menu.
Table 1
Electronic timer e.control.t08m
User’s guide and manual operation
EN
Parameter name
Value
Supply terminals
A1-A2
Rated voltage, V
AC/DC 24-264
Power consumption, W
1
Supply voltage tolerance, %
±10
Number of channels
single channel
Number of programs
80
Program
weekly program, daily program
Operation modes
manual, automatic, holiday
Summer/winter times
off, automatic changes
Time tolerance, °C
<1 s/day at 25
Power reserve, years
10
Data readout
LCD display
Number of contacts
1 C/O
Current of contacts, A (for AC-1)
16
Switching capacity, VA (for AC-1)
4 000
Mechanical life
10
6
Electrical life
10
5
Rated insulation voltage, V
250
Protection degree
IP20
Pollution degree
3
Altitude, m
2 000
Ambient temperature, °C
-20…+55
Permissible relative humidity, %
<50 (40 °C, without condensation)
Storage temperature, °C
-30…+70
Wire size, mm
2
1…4
Tightening torque, Nm
0,5
Dimensions, mm
90×36×64
3. Wiring diagram
First settings
Main menu
Time setting
Date setting
4. Installation and operating
•
The timer is installed in a plastic or metal box on a standard DIN-rail width 35 mm with latches having two fixed positions.
• Connect the power supply: L (+) to terminal A1, N (-) to terminal A2. Output normally open timer contact (terminal 18 – NO, 16 - NC 15 - com-
mon) is connected to the phase conductor breaking load power or break the conductor actuator power switching device, such as a contactor coil.
1 Press «MENU» key to enter main menu.
2 With «
▲▼
»
buttons select the desired item.
1 Select «
DATE
» and press «OK» key.
2 Select adequate hour with «
▲▼
» keys and press «OK» key.
3 Select adequate minute with «
▲▼
» keys and press «OK» key.
4 Exit from the setting by pressing «MENU» key.
1 Select «
DATE
» and press «OK» key.
2 Select adequate year with «
▲▼
» keys and press «OK» key.
3 Select adequate month with «
▲▼
» keys and press «OK» key.
4 Select adequate day with «
▲▼
» keys and press «OK» key.
5 Exit from the setting by pressing «MENU» key.