www.e-t-a.de
Electronic Circuit Protector ESX10-T.-DC 24 V
1822
3
4
Electronic Circuit Protector ESX10-T.-DC 24 V
Technical data (T
amb
= 25 °C, U
B
= DC 24 V)
Technical data (T
amb
= 25 °C, U
B
= DC 24 V)
Reset signal RE
with the falling edge of a + DC 24 V
terminal 22
pulse the electronically blocked
ESX10-TB-124/-127 can be reset via an
external momentary switch. A joint reset
signal can also be applied to more than
one device at a time. Devices in ON
condition will remain unaffected.
Control input I
N
+ ESX10-T-114
Electrical data
as reset input RE
Control signal I
N
+
+24 V level (HIGH): device is switched on
by a Terminal 21
remote ON/OFF signal.
0 V level (LOW) device is switched off by
a remote ON/OFF signal.
Switch S1 ON/OFF
device can only be S1 switched on when
a HIGH level is applied to I
N
+
LED indication
ON:
LED green
OFF:
LED red
General data
Fail-safe element
back-up fuse for ESX10-T not required,
due to an integral redundant fail-safe
element (protective element)
Terminals
LINE+ / LOAD+ / 0V
screw terminals
M4
max. cable cross section
rigid and flexible
0.5 - 16 mm
2
flexible with wire end ferrule w/wo
plastic sleeve
0.5 mm – 10 mm
2
stripping length
10 mm
tightening torque (EN60934)
1.5 - 1.8 Nm
multi-lead connection
(2 identical cables)
rigid / flexible
0.5 – 4 mm
2
flexible with wire end ferrule
without plastic sleeve
0.5 – 2.5 mm
2
flexible with TWIN wire end ferrule
with plastic sleeve
0.5 – 6 mm
2
Terminals
signal terminals
Screw terminals
M3
max. cable cross section
flexible with wire end ferrule w/wo
plastic sleeve
0.25 – 2.5 mm
2
stripping length
8 mm
tightening torque (EN60934)
0.5 - 0.6 Nm
Housing material
moulded
Mounting
symmetrical rail to EN 60715-35x7.5
Ambient temperature
-25...60 °C
1)
(without condensation, cf. EN 60204-1)
1)
ambient temperature range can differ
depending on approvals.
Storage temperature
-40...70 °C
Humidity
96 hrs / 95% RH 40°C to
IEC 60068-2-78, test Cab
climate class 3K3 to EN60721
Vibration
3g test to IEC 60068-2-6, test Fc
Protection class
housing IP20 EN60529
terminals IP20 DIN 60529
EMC requirements
noise emission EN 61000-6-3
(EMC directive, CE marking) noise immunity: EN 61000-6-2
Insulation co-ordination
0.5 kV / pollution degree 2
(IEC 60934)
reinforced insulation at operating area
Dielectric strength
max. DC 32 V (load circuit)
Insulation resistance
n/a, only electronic disconnection
(OFF condition:)
Conformity
CE marking
to 2014/30/EU
Dimensions (w x h x d)
12.5 x 80 x 83 mm
Mass
approx. 65 g