- 6 -
4 Accessories
4.1 Description
The ESX10-T features an integral power distribution system. The
following wiring modes are possible with various pluggable current
and signal busbars:
•
LINE +(DC 24 V)
•
0 V
Caution: The electronic devices ESX10-T require a
0 V connection
•
signal contacts
•
reset inputs
4.2 Accessories
Use original E-T-A accessories only!
l
Busbars for LINE+ and 0 V
max. load with one line entry
(recommended: centre line entry)
max. load with two line entries
grey insulation, length: 500 mm
X 222 611 02
l
Busbars for LINE+ and 0 V
grey insulation
max. number of plug-on operations 10:
X 222 611 22
(2-unit-block ESX10-T), length: 22 mm
X 222 611 34,
(3-unit-block ESX10-T), length: 34.5 mm
X 222 611 47,
(4-unit-block ESX10-T), length: 47 mm
X 222 611 59,
(5-unit-block ESX10-T), length: 59.5 mm
X 222 611 72,
(6-unit-block ESX10-T), length: 72 mm
X 222 611 97,
(8-unit-block ESX10-T), length: 97 mm
X 222 611 12,
(10-unit-block ESX10-T), length: 122 mm
l
Signal busbars for signal contacts and reset inputs
suitable for signal busbar ESX10-TB-...
max. load with one line entry
with one series connection of signal contacts Imax
grey insulation, length: 500 mm
X 222 005 03
l
Jumpers for signal contacts
suitable for jumper ESX10-TB-...
grey insulation, length: 21 mm
X 222 005 13
l
Insulated wire bridge
optional as jumper for ESX10-TB-101...
for group signalisation (series connection)
X 223 108 01
l
Connector bus link –K10
suitable for auxiliary contacts (series connection)
X 210 589 02 (1.5 mm2, brown)
3 Informationen on UL-approvals/
CSA-approvals
ESX10-TA / -TB
UL2367
Non-hazardous use
UL File # E306740
UL 508
Non-hazardous use
UL File # E322549
E322549
INDUSTRIAL CONTROL EQUIPMENT
ESX10-TA / -TB
ISA 12.12.01-2015
UL File # E320024
Operating Temperature Code T4
- This equipment is suitable for use in Class
Ⅰ
, Division 2,
Groups A, B, C and D or non-hazardous locations only. T4 A / 0
°C to 50 °C
WARNING:
- Exposure to some chemicals may degrade the sealing properties
of materials used in the following device: relay (K1)
Sealant Material:
Generic Name: Modified diglycidyl ether of bisphenol A
Supplier:
Fine Polymers Corporation
Type:
Epi Fine 4616L-160PK
Casing Material:
Generic Name: Liquid Crystal Polymer
Supplier:
Sumitomo Chemical
Type:
E4008, E4009, or E6008
RECOMMENDATION:
- Periodically inspect the device named above for any degradation
of properties and replace if degradation is found
WARNING – EXPLOSION HAZARD:
AVERTISSEMENT – RISQUE D’EXPLOSION
- Do not disconnect equipment unless power has been removed or the
area is known to be non-hazardous.
- Avant de deconnecter l’equipment, couper le courant ou s’assurer
que l’emplacement est designe non dangereux.
- Substitution of any components may impair suitability for Class
Ⅰ
,
Division 2.
La substitution de composants peut rendre ce materiel inacceptable
pour les emplacements de class
Ⅰ
, division 2.
This device is OPEN type equipment that must be used within a suitable
end-use system enclosure, the interior of which is accessible only
through the use of a tool. The suitability of the enclosure is subject
to investigation by the local Authority Having Jurisdiction at the time
of installation.
Wiring to or from this device, which enters or leaves the system enclosu-
re, must utilize wiring methods suitable for Class
Ⅰ
, Division 2 Hazardous
Locations, as appropriate for the installation.
ESX10-TA / -TB
CSA C22.2 No: 14 - File # 016186
CSA C22.2 No: 142 - File # 016186
CSA C22.2 No: 213
(Class
Ⅰ
, Division 2) - File # 016186
Class 2
Meets requirement for Class 2 current limitation
(ESX10-T...-0.5 A / 1 A / 2 A / 3 A)
Summary of Contents for ESX10-TA-DC 24 V