33
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Frame 12
Basis-ID+11
Standard:
70Bh
Contents
opState33 current33 opState34 current34 opState35 current35 opState36 current36
Unit
-
Ampere
-
Ampere
-
Ampere
-
Ampere
Conversion
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Data type
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Frame 13
Basis-ID+12
Standard:
70Ch
Contents
opState37 current37 opState38 current38 opState39 current39 opState40 current40
Unit
-
Ampere
-
Ampere
-
Ampere
-
Ampere
Conversion
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Data type
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Frame 14
Basis-ID+13
Standard:
70Dh
Contents
opState41 current41 opState42 current42 opState43 current43 opState44 current44
Unit
-
Ampere
-
Ampere
-
Ampere
-
Ampere
Conversion
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Data type
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Frame 15
Basis-ID+14
Standard:
70Eh
Contents
opState45 current45 opState46 current46 opState47 current47 opState48 current48
Unit
-
Ampere
-
Ampere
-
Ampere
-
Ampere
Conversion
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Coding
(2)
Divide
by 5
Data type
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
Unsigned
(1)
Coding of the input bit flags
0x0 OFF
0x1 ON
Most Significant Bit corresponds to input 32, least significant bit corresponds to input 1
(2)
Coding of the output status
0 OFF
1 ON
2 INRUSH
3
Alarm threshold reached (ALARM)
100 Short circuit (SHORT)
101 Overload (HIGHTRIP)
102 Inrush trip (INRUSHTRIP)
103 Low current (LOWTRIP)
200 Team trip (TEAMTRIP)
(3)
Coding of adjustment bit flag for current resolution
0
0.5 A
1
0.2 A (default)
If 0.5 A resolution was selected, the current values must be divided by 2 for conversion.