Electrical data of model 28
STAGE 1
STAGE 2
TOTAL
POWER TERMINALS
Tri phase 28.8 kW (*)
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
20.8
20.8
41.6
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
20.8
20.8
41.6
Relay K4 activated
Terminal 5
L3 (A)
20.8
20.8
41.6
Terminal 1
N (A)
0
0
0
Power
(kW)
14.4
14.4
28.8
Tri phase 21.6 kW
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
20.8
10.4
31.2
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
20.8
10.4
31.2
Relay K4 disactivated (**)
Terminal 5
L3 (A)
20.8
10.4
31.2
Terminal 1
N (A)
0
0
0
Power
(kW)
14.4
7.2
21.6
1
N
2
L1
3
L2
4
5
L3
6
1
N
2
L1
3
L2
4
5
L3
6
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase.
(*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.
- 9 -
TECHNICAL CHARACTERISTICS
Electrical data of model 22
STAGE 1
STAGE 2
TOTAL
POWER TERMINALS
Tri phase 21.6 kW (*)
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
20.8
10.4
31.2
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
20.8
10.4
31.2
Relay K43 activated
Terminal 5
L3 (A)
20.8
10.4
31.2
Terminal 1
N (A)
0
0
0
Power
(kW)
14.4
7.2
21.6
Tri phase 14.4 kW
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
10.4
10.4
20.8
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
10.4
10.4
20.8
Relay K3 disactivated (**)
Terminal 5
L3 (A)
10.4
10.4
20.8
Terminal 1
N (A)
0
0
0
Power
(kW)
7.2
7.2
14.4
1
N
2
L1
3
L2
4
5
L3
6
1
N
2
L1
3
L2
4
5
L3
6
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase.
(*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
Electrical data of model 36
STAGE 1
STAGE 2
TOTAL
POWER TERMINALS
Tri phase 36 kW (*)
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
26
26
52
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
26
26
52
Relay K4 activated
Terminal 5
L3 (A)
26
26
52
Terminal 1
N (A)
0
0
0
Power
(kW)
18
18
36
Tri phase 30 kW
Terminals 3 and 4 shunted
Terminal 2
L1 (A)
26
17
43
Terminals 5 and 6 shunted
Terminal 3
L2 (A)
26
17
43
Relay K4 disactivated (**)
Terminal 5
L3 (A)
26
17
43
Terminal 1
N (A)
0
0
0
Power
(kW)
18
12
30
1
N
2
L1
3
L2
4
5
L3
6
1
N
2
L1
3
L2
4
5
L3
6
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase.
(*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.