- 7 -
TECHNICAL CHARACTERISTICS
Electrical data of model 09
STAGE 1
STAGE 2
TOTAL
POWER TERMINALS
Single phase 8.4 kW (*)
Terminals 1 and 2 shunted
Terminal 3
L1 (A)
24
12
36
Terminals 3, 4, 5 and 6 shunted
Terminal 1
N (A)
24
12
36
Relay K3 activated
Power
(kW)
5.6
2.8
8.4
Single phase 7 kW
Terminals 1 and 2 shunted
Terminal 3
L1 (A)
24
6
30
Terminals 3, 4 and 5 shunted
Terminal 1
N (A)
24
6
30
Relay K3 activated
Power
(kW)
5.6
1.4
7
Single phase 5.6 kW
Terminals 1 and 2 shunted
Terminal 3
L1 (A)
12
12
24
Terminals 3, 4, 5 and 6 shunted
Terminal 1
N (A)
12
12
24
Relay K3 disactivated (**)
Power
(kW)
2.8
2.8
5.6
Single phase 4.2 kW
Terminals 1 and 2 shunted
Terminal 3
L1 (A)
12
6
31.2
Terminals 3, 4 and 5 shunted
Terminal 1
N (A)
12
6
31.2
Relay K3 disactivated (**)
Power
(kW)
2.8
1.4
4.2
1
N
2
3
L
4
5
6
1
N
2
3
L
4
5
6
1
N
2
3
L
4
5
6
1
N
2
3
L
4
5
6
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase.
(*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.