12. DC Wiring
A 6-way terminal block is provided on the DC beacon. There
are 2-off +ve, 2-off –ve, 1-off stage 2 & stage 3 terminals in
total.
Fig. 5 DC Terminals
12.1
Line Monitoring
On BExBGL2D DC units, dc reverse line monitoring can be
used if required. All DC sounders have a blocking diode fitted
in their supply input lines. An end of line monitoring diode or
an end of line monitoring resistor can be connected across the
+ve and –ve terminals. If an end of line resistor is used it must
have a minimum resistance value of 3k3Ω and a minimum
power rating of 0.5 watts or a minimum resistance value of
500Ω and a minimum power rating of 2 watts.
The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor
leads should be kept as short as possible.
Fig. 6 End of Line Resistor Placement
13. Flash Rate Settings
The BExBGL2D beacons can produce different flash patterns
as shown in Table 1. The flash patterns are selected by
operation of the flash setting DIP switch on the PCB, Fig 9.
Fig. 7: DIP Switch Location
Table 1: Switch Positions for Flash Patterns
Switch
Setting
S1 Mode
S2 Mode
S3 Mode
(123456)
(DC & AC)
(DC Only)
(DC Only)
000000
Steady High
Power
Flashing 1Hz
Flashing Triple
Strike
000001
Steady Low
Power
Flashing 1Hz
Flashing Triple
Strike
100000
Flashing 1Hz
Flashing
Double Strike
Flashing Triple
Strike
101000
Flashing 1.5Hz
Flashing 2Hz
Flashing Double
Strike
010000
Flashing 2Hz
Flashing Triple
Strike
Flashing Triple
Strike
110000
Flashing Double
Strike
Steady High
Power
Flashing Triple
Strike
001000
Flashing Triple
Strike
Flashing 2Hz
Flashing Double
Strike
Warning – high-intensity light source. Avoid
looking directly at the light source for
extended periods of time.
End of Line
Resistor
+
+
-
-
S2
S3