BExCP3C-BG 
Manual  Call  Point  –  Break  Glass 
With Resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres. 

 

 

1) 

Introduction 

The  BExCP3C-BG  is  a  break  glass  manual  call 
point  which  is  certified  to  the  European  and 
International  Gas  and  Dust  standards.  The  unit 
meets  the  requirements  of  the  ATEX  directive 
2014/34/EU and IECEx scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present.  
 
All units have up to two of the following: 

 

Monitoring resistors up to 1.5W per module 

 

Monitoring diode 

 

Monitoring Zener diode 

 
The units are Group II, EPL (equipment protection 
level) Gb. The equipment is certified ‘Ex db eb mb 
IIC  T4  Gb’  and  as  such  may  be  used  in  Zones  1 
and 2 with flammable gases and vapours with gas 
groups  IIA,  IIB  &  IIC  and  temperature  classes  T1, 
T2, T3 and T4. 
   These  units  are  also  Group  III,  EPL  Db.  The 
equipment is certified ‘Ex tb IIIC T75ºC Db’ and as  
such  may  be  used  in  Zones  21  and  22  for 
combustible dusts groups IIIA, IIIB & IIIC. 

 

2) 

Ratings & Markings 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 
 
Unit Type No.: 
BExCP3C-BG Manual Call Point 
 
Input Voltages: 

Important: 

See section 7.1 for current ratings 

 

125VDC Max    0.5A Max. Resistive Load;  

       0.03A Max Inductive Load 

75VDC Max      0.75A Max 
48VDC Max      1.0A Max 
24VDC Max      5.0A Max Resistive Load; 

       3.0A Max Inductive Load 

12VDC Max      5.0A Max 
6VDC Max        5.0A Max 
 
Code: 
BExCP3C-BG  
Ex db eb mb IIC T4 Gb 
Ex tb IIIC T75ºC Db 
IP66 
–40ºC <= Ta <= +65ºC 
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
 
Epsilon x:                           II 2GD 
 
CE Marking 
Notified body No.               2813 
 
Year/Serial No. i.e.20/1CP3CBG000001 
 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) 

Type Approval Standards 

The  call  point  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 
EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
The equipment is certified for use in ambient 
temperatures in the range  
BExCP3C-BG -40

o

C to +65

o

C  

and shall not be used outside this range. 

 

4) 

Installation Requirements 

Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14 

 

Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
Refer  to  certificates  SIRA  09ATEX3286X  and 
IECEx SIR 09.0121X for special conditions of safe 
use. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium  Pressure  Die  Cast  Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where used: Epoxy 
Resin 
 
If the equipment is likely to come into contact with 
aggressive substances, then  it  is the responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
“Aggressive  substances”  -  e.g.  acidic  liquids  or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 
 
 
 

 

 

View of base unit showing fixing centers. 
 
To  gain  access  to the mounting  holes  in  the  base 
the front cover must be removed. This is achieved 
by removing the 4 off M4 cap head bolts holding on 
the cover.          

 

 
Once the  screws  are  removed  the  cover will  hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 
 

6) 

Earthing 

The  unit  has  both  internal  and  external  earth 
terminals. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  a  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 

INSTRUCTION MANUAL 

BExCP3C Break Glass Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 